start	end	text
9240	15280	Hi, so my name is Tim Yardley. I'm here to talk about some work that I've done under
15800	23210	DARPA RADIX program. Whoa, I'm getting audio from somewhere. Hold on.
35120	38600	All right, sorry about that. I was getting feedback from the live channel.
39420	45500	So I am here to talk about building a cyber physical testbed and how we've used that to
45500	52120	support black start restoration under cyber fire. So this has been part of a DARPA RADIX
52120	56540	program. The RADIX program is Rapid Attack Detection Isolation and Characterization
56540	59760	Systems. And I'll talk a little bit about what that is here in a minute.
61300	69120	So just for sort of coverage and statement, the testbed work that I'm going to talk about
69120	73620	was funded under the DARPA's Rapid Attack Detection Isolation and Characterization
73620	78120	Systems program. I work for the University of Illinois. I'm the principal investigator
78940	85420	of the University of Illinois' effort under there. We also had some government SME support,
85420	92960	subject matter expert support from Idaho National Lab. And then the program evaluator
92960	98980	is a company called Probatech. And all three of those organizations have been critical to
99420	104240	the work that I'm talking about in terms of enabling the black star restoration efforts
104240	110120	and the validation of the work itself. So let's talk a little bit, give you a little background
110120	116120	on me. So my name is Tim Yardley. I'm a principal research scientist at the Information Trust
116120	123580	Institute at the University of Illinois. And I am also a father, a husband, and broadly a
123580	130880	researcher. I've been doing work in industrial control systems for about 14 years now. And I've
130880	140020	been doing work in security for, geez, probably almost 30 years now across the board. My
140020	149660	background came from sort of the think tank IRC eras back in the early days of FNET groups that
149660	156560	that, let's say, like to explore and like to figure out things, but also cause some havoc
156560	162560	in the process. I'm one of the original members of WooWoo and a variety of other security think
162560	170660	tanks over the years. And I've sort of been in the realm of computer security for
170660	176780	quite some time. I've been working in academia for about the past 12 years. And prior to that,
176780	182340	I worked in industry supporting a variety of different efforts. So the DARPA RADIX effort
182340	188520	itself, let's talk a little bit about what it is. So the program is designed to
189240	198100	build technologies that fill a gap. And that gap really is the notion that if we are
198100	204900	attacked by nation states, we are ill-prepared to be able to determine exactly what happened,
204900	208600	where it happened, and how it happened, and get rid of it as fast as possible.
208980	216280	So DARPA stood up this program to build technology that advanced that state of,
216280	223260	let's say, preparedness, and then to evaluate that technology on a realistic facility. And so
223260	229640	our role in that program was to build that realistic facility. We'll talk in more detail
229640	236460	about the objectives of the program itself. So these are all public slides from DARPA
236960	242640	that are here. But the key objective of the program itself is to enable black start recovery
242640	247380	of the power grid amidst a cyber attack on the energy sector's critical infrastructure. In this
247380	254260	particular case, the critical infrastructure is the electric power grid. So in a prevention
255400	261280	a sort of state, you would say, okay, well, let's defend and detect what's going on.
261280	267180	But this program starts from the adversary has been successful. So you have a complete blackout,
267180	272200	no power anywhere, and you have to figure out exactly what happened, how it happened, etc.
273640	280860	So the devices that are involved, you have to figure out what devices can be trusted,
280860	287820	because you don't know what's compromised and what is safe or what is operating per norm.
287880	295760	And many of the physical infrastructures are effectively controlled by intelligent devices.
295760	301320	So these are the ICS devices that you have to explore on, let's say, the cyber side of the
301320	309300	equation that are controlling the physical aspects of the grid. And these assets are spread throughout
309300	315460	the country. So how can you do this in a scalable way? How can you deeply and forensically poke at
315460	322220	these embedded devices? How can you figure out exactly what is trustable, what is not trustable,
322220	326240	what was attacked, how it was attacked, and then get rid of it as fast as possible.
326240	332820	The goal is to do so across the entire United States within seven days. And that's to isolate,
332820	340480	characterize, and restore any crank paths necessary to bringing the grid for the United States back online.
342360	349600	So let's talk about the manifestation of this. So in the first year or so, year and a half of the
349600	355020	program, we built exercise environments that were run at the University of Illinois that were
355020	361160	getting people's feet wet and getting the technology ready to explore, let's say, the beginning
361160	368200	edges of the problem space. And as we evolved both the technology and the program,
368200	376140	we had to turn the corner. So people will only believe what happens in a lab to the extent that
376140	383520	it's, oh, that was in a lab environment. Oh, that's fine if you do it just on science. But that's not
383520	390340	the real world. So we took it to a federal island, which is called Plum Island. It's the home of the
390340	400400	Animal Disease Center, controlled and owned by DHS, S&T, and is a former siting of Fort Terry in
400400	405160	the Spanish-American War and a bunch of other stuff. The size of the space that we're controlling
405160	410920	there is roughly the size of Central Park. And we have built electrical infrastructure on that
410920	417400	island. And so I'll talk about the most recent incarnation of it that was completed in November
417400	423920	of 2019. That was the sixth exercise of the program. We have one more exercise still to do.
423920	430000	COVID has postponed that a little bit, but still pending. So far has not been fully canceled.
430440	437660	And we look to sort of do that last hurrah of the program and validate the advancements from
437660	445740	the last exercise till now. So in the island infrastructure, we basically have built three
445740	451100	full utilities. And those utilities are represented by gear that we'll talk about here
451100	456620	in a moment. They have an emergency operations center for each utility. And then there's a
456620	461340	regional coordinator that's trying to coordinate the actions amongst the different utilities as
461340	468480	it goes through. We have the National Guard involved. We have the RADIX performers involved
468480	474980	and lots of other entities that help establish communications in a variety of way and really set
474980	483940	up what is a fairly austere environment from the beginning to enable the capture and execution of
483940	490660	these exercises. So utility A has five low voltage substations. And I'll talk about what low voltage
490660	497760	means to us. And one high voltage substation. It also had one generator, which is the crank path,
497760	503080	in essence, that's getting to the high value assets. Utility B had seven low voltage substations
503080	508560	along with three high voltage substations and that crank path had a critical national asset
508560	516320	on it that needed to be up and maintained no matter what. Utility C was similar to utility A.
516320	521880	It had five low voltage substations and one high voltage substation as well as one generator. And
521880	527760	so each of these utilities differed in the physical topology and layout of the substations.
527760	532300	They also differed in the equipment that was deployed across each of those substations.
533700	541060	So the program is really broken into multiple different technical areas. You could look at it
541060	546940	as four or five depending on how you want to count. The first area is situational awareness.
546940	551120	And so when they deploy on this infrastructure that we've built, they are trying to figure out
551120	556960	what happened or what is currently happening on the infrastructure to get as much situational
556960	561520	awareness as you can provide. And the reason for that is you can't really trust the devices once
561520	567000	they've been attacked to be telling you the right things. And you are in a blackout scenario,
567000	574120	so you may not have visibility in much of the grid environment. Network isolation is technical
574120	582400	area two. And technical area two is focused on taking the communications that are no longer
582400	590680	necessarily trustworthy and expanding those into a realm of trustable or not. And so by that I mean
591240	597560	point A to point B may have talked to each other before. And it used to be a dedicated private link
597560	605180	or whatever it may be. But now traffic that's going across there is not reflecting what it
605180	609400	did previously. So maybe somebody's man-in-the-middle-ing it. Maybe somebody is manipulating
609400	615120	it. Maybe it's getting black-holed in some other way. Unknown operation, right? So how do you take
615120	621740	the outputs from A and get it to B in a way that's trustworthy and secure and such that it
621740	628580	cannot be modified in the middle or that it is evident when it is modified in the middle? So
628580	635640	that's the area of research for technical area two. Technical area three is threat analysis.
635640	642900	And they really are intended to do the forensic response per se on the devices itself. So how do
642900	649680	you diagnose and remove cyber threats from the embedded devices, from the different pieces that
649680	659560	are involved, et cetera, as you go through the investigation part of the environment? So the
659560	664880	environment itself is technical area four. And that's conducted by us at the University of
664880	672380	Illinois. And that is the environment by which the exercise happens, which is on Plum Island,
672380	678440	but also the environment at the University of Illinois' campus that the performers remote into
678440	683260	to build out their technology, to extend their capabilities, and to investigate
684080	689680	the edge cases of how the grid operates when certain things happen to these devices.
690700	695180	So that's part of our central facility, and I'll talk a little bit about that. And then the island
695180	701960	is basically a distributed manifestation of that central facility at Illinois. The last
701960	707160	technical area is technical area five. And effectively, that is the evaluators of the
707160	716200	program. And they build out how to run an exercise in this space and how to determine whether or not
716200	723480	progress is being made on the technology, what the appropriate challenge levels are, the, let's say,
723480	731240	pain points, or how deep or how hard the red team pushes, et cetera, as we go through the environment.
731240	738480	And they technically grade technical areas one, two, three, and four as they go through that.
739980	750500	So on to the next slide. RADIX exercise six was really a move from strategic to the strategic
750500	756600	notion early on in the program to operational notion with the utilities involved, et cetera,
756600	763300	to a tactical deployment on top of that. So if you look up in the upper left-hand corner,
763300	768060	the strategic notion is the concept that we talked about of you have a large-scale blackout and what
768060	775060	you need to accomplish. The operational notion is the building and establishment of these crank paths.
775060	780580	And then the tactical is let's execute on those crank paths and figure out exactly what happened
780580	787420	and how it happened. So the picture on the bottom right at the moment is a drone footage
788600	794740	sort of zoomed in on one of the substations. And you can see that they're built in shipping
794740	800520	containers. And those shipping containers have gear inside them that I'll show you here in a moment.
800540	806380	And then these containers are arranged and linked together to build the crank path. And we do that
806380	815320	with basically above ground number two SO cord that has connectors on the end that we plug into
815320	819780	to the individual gear that we have inside the boxes. And I'll show you what that looks like
819780	828080	here in a moment. So you can see sort of a little bit of an edge here of what is inside a container.
828080	833980	So this is standing inside a container looking out at the moment with the door open. So on the
833980	838420	left-hand side there, you'll see what we call the relay box. On the right-hand side, you'll see what
838420	845180	we call the power box, which is a skid-mounted Hoffman enclosure that controls the flow in
845180	851720	essence of the substation. So that's the power grid aspect. And the controls of those grid
851720	859080	components are in the relay box on the left-hand side. There's also some sensors that are up on top
859080	863600	that are providing or that are performer technology, providing some of the situational
863600	868280	awareness and attempt to determine ground truth as we go through the environment. And I'll zoom
868280	874600	in on a lot of this as we talk. So I'm going to only talk about the testbed itself. I'm not
874600	880120	going to talk about any of the performer technology that's specifically built, but I'll
880120	885980	dig quite deeply into the testbed, which is my area of responsibility. So the mission that we set
885980	892620	out to do is to provide realistic environments that enable this cutting-edge R&D that's not yet
892620	901100	done by any commercial available product or any existing research off the shelf. And then we take
901100	906660	and create this environment in a way that allows us to validate the effectiveness and frankly,
906660	914040	the efficiency of those tools as we go through. So the goal of the program itself is really to
914040	920700	take a generational leap forward in the capabilities of testbeds. So we've been building
920700	926520	cyber-physical testbeds and leveraging the cyber-physical testbeds for about 13, 14 years now
926520	932200	at the University of Illinois. By many accounts, we're sort of the gold standard in terms of
932200	940740	capabilities across the nation and arguably the world. But even so, when we pitched our
940740	950230	capabilities for this program, our proposal and the going in salve of our proposal was effectively,
951160	956580	we have assembled the right team to solve this problem. But what technology exists today and
956580	961580	where testbeds are today across all of them that you will encounter and anyone that bids,
961580	965660	all of them are woefully inadequate to be able to actually go to the level of
965660	969620	realism that will be necessary to validate these tools.
970080	976820	And even with us, it is an extreme long shot as to whether or not this will be achievable
976820	982960	in the time frame and advancing fast enough to be able to support this post-attack analysis.
983040	987560	And so let me riff on that for a second. Cyber-physical testbeds before this program started
987560	992580	were primarily focused on let's either build an environment where we're looking purely at a
992580	998400	physical phenomenon, or let's build an environment that's proving out a hypothesis,
998980	1005580	physical or cyber, and look at it from that particular angle, sort of ignoring all of the
1005580	1012120	other details. But in this program, everything is unknown coming in. You don't know what the
1012120	1017380	attackers did to you. You don't know even what the attackers want to do to you on the environment. So
1017380	1023600	you have to have every piece of it as real as possible. But you can't possibly go build, you
1023600	1032800	know, three real crank paths and 24, 27 real substations out there because it just costs way
1032800	1037560	too much money to do. And it's a dangerous environment to be in. So how can you minimize
1038380	1046180	the environment, maximize the safety, and also maximize the realism without running into problems
1046180	1052740	of naysayers with simulation being involved or emulation of devices, etc. So they need to be
1052740	1057880	able to touch it, they need to be able to feel it, they need to be able to see it, and they need
1057880	1064260	to be able to trust that what it does and how it works is going to be reflected or reflective
1064840	1072680	of what happens in the real world. So the outcomes of the testbed work itself, obviously we've
1072680	1077700	created a lot of tools, we've pioneered some new techniques and methodologies, we've combined
1077700	1083400	existing solutions, both that we've had and that others have had, to build an environment
1083400	1087800	together. And we combined that, not just the academic knowledge that we had at the University
1087800	1096520	of Illinois, but in partnerships with key vendors and also with asset owners and
1096520	1102580	operators, and to build really an environment that reflected not only the real world, but
1102580	1110860	that took a whole leap forward on its ability to evaluate research. So what is a testbed?
1110860	1117540	So a testbed really is somebody has a need, let's call them the customer, and that need
1117540	1124300	is to evaluate something. And so a testbed is assets, the thing maybe that they want to evaluate
1124300	1129080	on. It's the people with the knowledge on how to build that environment in the way that
1129080	1134740	represents the scenario they need to look at, etc. What to capture, how to capture, where to
1134740	1140860	capture it, etc. It's the science of how to do so in a realistic way, while still enabling the
1140860	1146360	necessary data capture that sometimes these systems inherently don't support. And then it's
1146360	1152740	that data itself. And that data itself is what is captured from the devices, either willingly or not.
1152740	1157740	How the system was operating, packet captures as an example of the communications that are going
1157740	1163000	across, ground truth as to the physical telemetry of what was actually going across, not just simply
1163000	1170400	what the devices are reporting is happening. And then a manifestation of or configuration of all
1170400	1177280	of those things together that is provisioned out into an environment that you then do the work on.
1177280	1183180	Our capability, we can provision locally the assets in our central environment. We can
1183180	1188920	provision portable environments like what we've built on Plum Island and deploy on Plum Island.
1188920	1192740	And we can also provision into the cloud in a variety of different ways.
1193600	1201100	So why a testbed? What's the value of a testbed? You've seen, obviously, the ICS Village and
1201100	1206280	Capture the Flag stuff. But this is a little bit different. And the reason for a testbed,
1206280	1210620	the reason for the work that we do, is that this mission-critical technology,
1210620	1214680	and why do I call this mission-critical technology? So the technology being built
1214680	1224300	under RADIX is intended to be, let's say, have its glass broken when we're in a blackout scenario,
1224300	1229700	effectively, after we've been hit. That's where the real value of this technology is.
1229720	1234660	And there's arguments, and I am one of the people that will argue this, that that technology needs
1234660	1241500	to be used even before we're hit. But in the end, our grid is down. That's what this technology
1241500	1247140	is built to solve. And so it is absolutely essential, if this technology is called to
1247140	1253320	practice, that it works, and that it resolves the issue, or that it can figure out what's going on
1253320	1258560	in the issues, etc., before we need it. Because if we don't, and we're in a national blackout,
1258560	1267560	national disaster sort of scenario, attacked by an enemy or otherwise, how do we come back if we
1267560	1273300	break the glass on this technology, and it's not been proven to actually work? And so you run it,
1273300	1277780	and it's like, I can't figure out what's going on. I see nothing wrong. There's no problems here
1277780	1283940	whatsoever, but the devices still won't turn on. The grid still is down. These devices aren't
1283940	1289620	operating correctly. And that's a bad scenario to be in. So this is truly mission-critical
1289620	1293960	technology, and we have to prove that it's effective before we need it. But we have to go
1293960	1298800	beyond the theoretical testing of it. We have to put it in all sorts of scenarios across all sorts
1298800	1304600	of different platforms to verify that it works, even in edge cases that it wasn't expecting,
1304600	1309220	in circumstances where it's missing data, in circumstances where it's even being directly
1309220	1318280	attacked or attempted to be, let's say, misled on what is going on. So our solution for that is
1318520	1323720	a realistic, recomposable, and well-instrumented testbed is essential to being able to prove that
1323720	1328660	out, because even the real grid environment cannot be manipulated in the way that we can
1328660	1333200	with a testbed environment. And I'll talk a little bit about some of the innovation in that space.
1333820	1338840	And frankly, everything, as I started with my opening salvo and the proposal, that existed,
1338840	1343780	including the Illinois capabilities, wasn't good enough before this program started.
1344560	1352220	So our approach across it is to build real systems. We also build models, looking at models
1352220	1358720	on the cyber side and physical side, that adapt to the exercise needs, that help us build out
1359400	1365020	behaviors and changes in the flows and the communications of systems, to operate like
1365020	1370400	the real world or to operate in a way that an adversary may be able to manipulate.
1370860	1377520	Everything is built in this modular way. It's adaptable and, let's say, recomposable in a
1377520	1382380	variety of different ways. So we can take a piece and take a substation and how it's physically
1382380	1387820	wired and physically set up at the moment, press a couple buttons, push a different configuration,
1387820	1393860	and now it's a different substation. Same devices, different configs, different network layout,
1393860	1401140	etc. And all of that adaptability or modularity allows us to recompose the system in any way
1401140	1407580	necessary to present different challenges, etc., as we go through. There's also instrumentation.
1407580	1413640	And so the instrumentation is key in that many of these systems, let's say, will cooperatively give
1413640	1418620	you a certain amount of data. But sometimes when you're doing forensic analysis, you need to be
1418620	1423600	able to gather things that are deeper. Or if you're trying to do experimental validation,
1423600	1429180	you need to be able to look at things that the system inherently won't tell you. Or you need to
1429180	1433100	look at it with much more scrutiny than what you would typically look at in the real world.
1433100	1440240	So how do you do that and turn on an appropriate level of data output, data capture, etc.,
1440240	1445660	but that doesn't actually affect the behavior of the systems? Because sadly, some of these systems,
1445660	1451680	as you may know, are underpowered. And if you turn on, let's say, full complete logging of the system
1451680	1457120	or other things, it can bog down the operation of the system. And then it no longer participates
1457120	1465840	or acts as it would in the real world. So the last part is really knowledge. And by that, I mean,
1465840	1471900	we don't just say, look, as academics, we're bright people, trust us, this works. We had to bring in
1471900	1478200	real operators. We had to bring in the manufacturers, the vendors across many different
1478200	1484040	platforms and talk through with them their best practices, their common misconfigurations that
1484040	1491000	they see when integrators are building their platforms, the common ways that they configure
1491000	1499060	their substations in the real world for the asset owners, etc., to both cause, let's say,
1499060	1503340	human error to happen in ways that people accidentally misconfigure things,
1503340	1508180	but also to mimic as closely as possible how people are actually configuring these in practice.
1508200	1514720	And that is to get the right level of protection, the right level of output of data, and even notions
1514720	1521260	of like, okay, what does a SIP-compliant substation look like in terms of what it is logging or not,
1521260	1526340	versus one that's not. So that all comes together in that knowledge area.
1527220	1536100	On the innovation side, we had to innovate quite a bit. And so the, let's say, orchestration or
1536100	1544520	automation stuff that we had previously was good enough for research, but it made a lot of
1544520	1549400	assumptions. And so by that, I mean, it would operate in a centralized environment, but when
1549400	1555520	it tells something to be reconfigured or tries to control something, it expects that, A, the device
1555520	1562900	is reachable, B, that it has access to that device, that it has the credentials to get on that device.
1562900	1572160	It assumes, I guess, C, that it knows what the state of that device is. And then lastly,
1572160	1576140	everything that it did before, it also assumed that the device was trustworthy
1576740	1583820	and in a known sort of condition. So we had to, let's say, break down all of those assumptions
1584340	1592240	and operate in a way that, let's say, didn't rely on any of those existing substations.
1592240	1600500	We applied a bunch of research as well. Obviously, we had over a decade of work in the
1600500	1607460	prevention space and in the detection space and remediation space at the University of Illinois.
1607920	1612860	And we had used that in the testbed in a variety of ways. We had used it or proved it out in the
1612860	1617980	testbed, some of which is even in formal companies now transitioned either to big vendors or as
1617980	1622840	startups. And we had to apply that in sort of a different way as part of the testbed,
1622840	1629100	not to just say, okay, look, here's the testbed environment. But for instance, if we could reach
1629100	1634680	deeper into a device, then we used some of that research that we had to dig deeper into those
1634680	1639520	devices and pull out and extract information that supports the validation of the technology
1640080	1649300	without affecting the performance of the device itself. Our team, in particular, myself and a few
1649300	1656580	others have went really deep on some of these platforms over the years. And so we brought a
1656580	1663540	wide variety of devices to the table that we already knew quite a bit about on the inside.
1663540	1668740	Sometimes even, let's say, one could argue more than what the vendors know about their own devices.
1669600	1674900	In terms of the knowledge and ways that we could poke around inside of these platforms.
1675440	1680860	We had to also build, because we needed to deploy on an austere environment,
1680860	1687240	if you don't have it, then you better bring it type notion. And so we had to build these boxes
1687240	1693060	in a way that were field serviceable. We had to be able to quickly replace components of the system
1693060	1698680	if it were to break or if the intent of the cyber attack against it was literally to brick it so
1698680	1704880	that it was no longer functional. How did we restore that or replace that in as fast of a
1704880	1711680	situation as possible to move on and not basically stop the whole exercise if something were to break?
1711680	1718440	We had to advance our automated configuration, data extraction, and also the notion of the system
1718440	1724440	and its observation when even the network links were no longer trustworthy or reliable to be up
1724440	1729180	or down. Remember, we're in a black start scenario, so we're not even guaranteed that
1729180	1734020	we'll have power on each of the substations to be able to communicate to them. And when they're
1734020	1740140	brought up, we need to maintain the state of everything we captured as they go up and down
1740140	1748560	like a seesaw as they're being attacked and brought up and brought back down, etc.
1748640	1753840	And then we also needed to have the environment in a way that could be recomposable, change the
1753840	1758660	structure of the crank paths, change the behavior of the substation itself, without going through
1758660	1766320	and recabling or rewiring everything that's in there on a hands-on nature. So what are these
1766320	1773680	environments? So combined, I call them the substations in a box. It's two components.
1773680	1778780	This has been built on the extensive facilities we have at the University of Illinois that I've
1778780	1784420	alluded to. We have roughly $100 million worth of hardware and software at the University of
1784420	1790840	Illinois that have been built up over the past decade plus, much of which by donation.
1791120	1796160	That's enabled all sorts of research that we've done in the past with Trustworthy Cyber
1796160	1801860	Infrastructure for Power, which was an NSF effort, a DOE DHS effort called Trustworthy Cyber
1801860	1808140	Infrastructure for the Power Grid. It added grid to the end. Our most recent center that's wrapping
1808140	1813480	up in the next year or two called the Cyber Resilient Energy Delivery Consortium,
1813480	1819420	which is also DOE and DHS funded. Our Critical Infrastructure Resiliency Institute,
1819420	1825720	and a variety of other things that have and leverage the testbed resources at Illinois.
1826520	1831240	So the substations in a box, as I mentioned, they're designed to support this Blackstart
1831240	1836360	crank path analysis and deployed in the field, real grid environments built, etc.
1836360	1841460	They're built in pelican style cases, so they're literally shippable and deployable anywhere we
1841460	1851100	need to stand them up. They're generally mostly IP55 watertight when they're shipped and moved
1851100	1857340	around. When you physically deploy them, we take the case lids off and put them in enclosures.
1857340	1863540	The reason for that is literally so the devices inside don't overheat, but also because you do
1863540	1868720	need some physical access to the devices to control breaker operations and other aspects.
1869120	1876200	We built an environment on an island, so the power infrastructure of what is in the overhead
1876200	1882700	and underground stays, but basically everything else gets torn down and built back up every six
1882700	1888680	months in a different way. There are currently 26 variants of substations deployed across
1889260	1896180	that infrastructure. Those substations have relays, RTUs, substation network switches, routers,
1896180	1902340	as well as an experimental fabric underneath that's controlled by SDN that allows us to do
1902480	1908520	a lot of the capture and, let's say, dynamic changes of the substation itself. All sorts of
1908520	1914300	protocols are deployed. You can see a list of them up on the screen. There's both serial and
1914300	1919840	Ethernet communications. We have custom power connections on the power boxes that allow us to
1920620	1926460	link these systems together in a safe way. And then we have high-voltage infrastructure that
1926460	1933400	I'll talk about as well. So what's a power box and what's in a power box? So power boxes basically
1933400	1941440	think of it like the physical infrastructure of the island or of a real substation. So that's
1941440	1947040	the breakers, the bus bars, the incoming and outgoing feeders on the system. We have a local
1947040	1952900	load feeder as well. We have signalization lights that indicate what the status is of energization,
1952900	1960780	what the status is of breakers. We have a dead bus sync light that's provided. We have analog
1960780	1969500	sync check relays, contactors, auxiliary contacts on the systems, CTs and PTs, control circuitry
1969500	1973740	behind that allows us to operate breakers and various other stuff. We have different modes of
1973740	1979700	operation, sort of a safe mode where we can walk away from the system and the system can't possibly
1979700	1987360	change, which is a sort of a unique scenario differing from the real world. And then we
1987360	1993280	obviously have the ability to locally control breakers as well. So what does that look like?
1993280	1999060	So there are effectively two types of power boxes inherently that we've built.
1999060	2005900	One is a 208 volt three-phase system. One is a 480 volt three-phase system. They look
2005900	2010820	basically identical from the front, except for the size of them is a little bit different.
2010820	2016620	We also have these high voltage systems, which really are Hoffman enclosures that
2016620	2025840	are wall mounted and act like, let's say, semi-intelligent breakout boards for providing
2025840	2030800	telemetry from the high voltage gear to the corresponding devices that are then operating
2030800	2036660	and controlling that high voltage gear. And so think of it sort of like a mapping board
2037220	2046060	in a way. And each power box generally has an incoming circuit, a load circuit, and then two
2046060	2053820	outgoing circuits as it's built out. So basic electrical diagrams in the middle, but nothing,
2053820	2059940	let's say, shocking about that. And then there's the other side of it. And so each of these devices
2059940	2065840	have the number two SO cord coming into these Hubble connectors on the edge. But they also have
2065840	2072040	umbilical cords, which are amphenol connectors, mil-spec amphenol connectors, that basically take
2072040	2077280	all of the telemetry of what is happening on inside the box and provide that telemetry to
2077280	2082760	the devices that need to control it. So that includes the analog and digital signals that
2082760	2090420	need to be sent back and forth between the devices to control them, but also the CTs and PT outputs,
2090420	2096100	etc., from the system itself so that all of the sensing is detectable by the relay boxes.
2096180	2101180	And so what are the relay boxes? Well, the relay boxes are really the brains of the substation. So
2101180	2107660	here are a couple examples showing some of the different technology that's in play. Up in the
2107660	2116240	upper left, those are ABB relays along with an ABB RTU. This is sort of a legacy RTU platform
2116240	2123200	that ABB leverages or uses and has deployed around the world called the RTU-560. In the middle,
2123200	2130380	you'll see some more ABB relays, middle-top. And above that, instead of an RTU-560, you see a
2130380	2137080	Motorola device. This is a Motorola ACE-3680. If you move to the next image, upper right-hand
2137080	2145920	corner, that is an ABB COM-600 rack mount or a COM-600R that is acting as the RTU over those
2145920	2152840	ABB relays that are there. Bottom left-hand corner, you'll see some touchscreen SEL-751 relays. Those
2152840	2161500	are controlled... the RTU in that particular case is an SEL-RTAC, a 3505. In the middle,
2161500	2168200	you'll see touchscreen relays. In that one, there's an SEL-RTAC as well, but that's an SEL-RTAC.
2168200	2177000	It's a SEL-3530 instead of a 3505. And then the far right, you'll see more SEL relays. These
2177000	2181880	ones are not touchscreen. These are another variant of the SEL-751. And those ones are
2181880	2189280	being controlled from an RTU perspective by a Novatek Orion LX. So this shows just some of the
2189280	2197040	diversity of platforms that are there. There are much more, obviously, across 26 substations.
2197400	2203120	Every single substation is unique in some way, shape, or form. So we have a lot of diversity
2203120	2209060	across the environment in terms of platforms, technologies, and configurations. And so
2209060	2213800	diversity could be purely on the configuration side. For instance, different protocols being
2215560	2224260	communicated, different topologies being set up between Utility A, Utility C, Utility B, etc.
2225420	2232480	And lots of other variation on top of that. So let's talk about some, let's say, lessons learned
2232480	2238820	from the program or challenges that we had to tackle, now that you understand some of the gear.
2238820	2246820	First off is safety. When you can't trust anything in the system whatsoever because it is compromised
2246820	2252640	and it's compromised in a way that you may or may not know, may or may not be able to determine,
2252640	2258280	and you don't know what is trustable or not, all of the systems that are there are effectively
2258980	2264840	designed to protect you. But if you can't trust the digital systems to protect you anymore,
2264840	2269160	then you need additional layers of protection. So we had to layer protection throughout the system
2269160	2275300	in both physical and cyber form. And that included things like analog time,
2276900	2282920	analog protections in the system, like analog sync check relays, time over current protections,
2282920	2288700	thermal protections. On the digital side or on the cyber side, the protective relays were configured
2288700	2296420	with safe and sane settings for overvoltage and undervoltage conditions, etc. The boxes had arc
2296420	2302460	flash analysis done on them to determine potential exposure or safety measures from PPE perspective
2302460	2307820	that needed to be done. The cabinets were all either pad lockable or direct key lockable.
2307980	2313900	We had, on the high voltage side, interrupters that were acting as fail safes if there's anything
2313900	2319520	that flows through. The low voltage to the high voltage side, an out of sync close or something
2319520	2325840	like that that happened to happen, or a surge somewhere, the interrupters or a fault on the
2325840	2331260	line, the interrupters were there to protect the system at the high voltage side. We also
2331260	2338780	purposefully did not target the high voltage control. That way we didn't run into, let's say,
2338780	2344840	big issues. Low voltage was something we could cause a problem on and be okay with, but on the
2344840	2350960	high voltage side people could get hurt. All of the connectors we used were screw-in locking style
2350960	2357680	connectors. We had all sorts of internal wiring protection, etc. So the key is that the environment
2357680	2363860	itself was designed to be safe no matter what. So people that knew nothing about power systems
2363860	2370180	could still safely operate in this environment and not run a risk of being electrocuted or
2370180	2376140	whatever. We always had power engineers and safety officers effectively on site that were making sure
2376140	2382560	that people did safe operations and maintained the necessary perimeters, even at a noise level
2382560	2393840	from the generators and various other aspects. But really the system protected itself in every way,
2393840	2400780	so let's talk about some operational lessons that we learned in executing exercises for
2400780	2407540	blackstart restoration, but also in austere environments under conditions of blackouts,
2407540	2413780	etc. And so let me talk a little bit about the mode of execution as we go through this. So
2413780	2418580	when I say that we're operating utility environments, we are actually operating
2418580	2424760	the utility environments. And by that I mean utility operators from real utilities come to
2424760	2432460	the island and they run the infrastructure. And they basically take control of it, we hand it
2432460	2437580	over to them, and then they tell everyone else what to do, how to do it, when to do it, etc.
2437920	2444720	on the system. Now obviously we have some exercise control over that, but the intent is to really
2444720	2451020	make this as real as possible. So let's talk about that realism. Many people don't believe
2451020	2456420	what is possible until it really is, let's say, slapping them in the face. And by that I mean
2458300	2465320	a common view is, look, relays, they're embedded devices, you can't make them do things, you can't
2465320	2472540	disable their protection, you can't change their mode of operation beyond their config.
2473220	2479000	And until they saw us do that, they didn't really believe it. Even when it was happening
2479000	2483920	right in front of them, they still didn't believe it until they dug deeper and started to look
2483920	2488880	deeper at what was happening and how it was happening to realize that, look, bad things
2488880	2495440	really are possible, that right now your mindset is that this isn't possible at all, that no one
2495440	2500760	can do that. You had to physically modify the device in order to do that. And it's like, no,
2500760	2507540	we can actually do that via cyber means. So let's talk about the people, right? One of the things
2507540	2514320	that was an operational lesson is academia is really good about thinking outside the box,
2514320	2521360	but we needed to be extremely agile and think even further outside of the box and push through
2521360	2530400	and build stuff that, frankly, was, let's say, impossible to build at any given moment.
2530400	2537640	We took on building one utility, then two, then three, all in six-month iterations. Completely
2537640	2543360	different architectures, completely different devices, building the physical boxes, and
2543360	2550320	standing it up in a new realistic configuration at each sort of interval. That's pretty difficult
2550320	2556060	to do. It's multiple weeks to build the environment each time. It's multiple weeks of testing. It's
2556060	2560760	multiple weeks of evaluation to make sure that it is as real as possible, that it doesn't have
2560760	2567580	inherent artifacts itself that people may view as compromises, etc., in the system, that it is
2567580	2575200	pristine, blue sky, trustable, etc., and built the way it should be built. And that results in,
2575200	2581660	let's say, extreme levels of stress at times, but as a team, not just the University of Illinois,
2581660	2586920	but broadly the entire program, we all pulled together and found success in every exercise that
2586920	2593260	we had. There was no exercise that failed because the infrastructure or the people failed to deliver.
2594700	2601660	And so that brings us to pace. So I mentioned every six months. So DARPA programs move very
2601660	2607820	fast, and the expectations are very high of the technology, of the evaluation, of the test bed,
2607820	2616820	etc. And so there were many times that we were facing failure. But let's say by pure blunt force,
2616820	2625800	and by pure blunt force, I mean number of hours and long days and leveraging and leaning on each
2625800	2632180	other throughout the program, we were able to pull through and pull off what seemed to be impossible
2632980	2639420	when we started. So those are some just operational aspects that we learned as we
2639420	2645060	built the environment, especially out on an island. And so when I say, you know, what are some challenges,
2645060	2651240	right? So there were times when we were, you know, we took a ferry every day from the mainland to the
2651240	2656360	island, and there were times when, you know, nor'easters were blowing in and other aspects where
2656360	2664820	the waves were 12, 14 feet high, and the, you know, conditions were such that if you go to the island,
2664820	2669820	you're going to be sleeping there because you're probably not going to make it off. And that's
2669820	2676360	kind of, you know, let's say a bit much, but there were many days that happened like that.
2676360	2681740	There were days we were out there executing the environment, trying to restore after the cyber
2681740	2688480	attack, and, you know, there was nor'easters blowing through with 40 plus mile an hour winds
2688480	2695740	and downpours and inches of rain falling an hour, etc. So not just hard from a technical perspective,
2695740	2702060	but even harsh environments that we were out in as we were trying to restore these devices,
2702680	2706580	and as the teams and the utility operators were operating these devices
2707380	2712320	faced with those types of environmental conditions. So we learned a whole bunch of
2712320	2720540	other lessons too. So one of them that was interesting to us was that when the systems
2720540	2725940	are intended to break, when you know that you can't trust anything anymore, you have to think
2725940	2731580	differently about what you can build and how you build it so that it works consistently and reliably
2731580	2736760	even when everything is intended to be broken. So that goes back to some of the stuff we did
2736760	2744020	with safety, but also on the cyber side. So as an example, we had no guarantee of power,
2744020	2749780	reliably or not, at any point in time. So how do we guarantee we don't lose data,
2749780	2756040	as an example, as we're going through, or that we get, let's say, eventual consistency where
2756040	2761400	if part of the network is up and being controlled by our orchestration and another part of it is
2761400	2767840	down, how do we get it to catch back up and get in the right configuration when it does come back up
2767840	2773440	if it needed to be changed, or to collect all of the data that it had when it wasn't centrally
2774400	2781560	reachable, when it was isolated and only, let's say, on backup power on its own. So that presented
2781560	2786520	some interesting challenges that we had to tackle, which is basically fault-tolerant and distributed
2786520	2793220	computing in a nutshell. The other issue that was somewhat interesting that we had to
2793220	2798820	innovate on was the gear in the field typically isn't hot swappable. You can't just go grab a
2798820	2803700	relay that's in a real substation and pull it out and pop another one in, in most of the substations,
2803700	2811000	without having to do some rewiring, without having to take circuits out of commission,
2811000	2816140	de-energize them, lock out, tag out procedures, etc. But if you're in a fast-paced exercise
2816140	2821340	environment, we have seven days, and if people get stuck and we need to reverse out basically
2821340	2827440	what the bad people did, how do we reverse that out in as fast a way as possible without bringing
2827440	2833200	the whole exercise down or the whole exercise to a halt for hours on end? So we had to create
2833200	2837440	sort of quick connects and all sorts of other things that allowed us to swap gear out very,
2837440	2845080	very quickly. Further, when we're testing bleeding edge technology, things fail because sometimes
2845080	2851160	that technology doesn't work, or the research doesn't do what it's supposed to do. And so
2851160	2855300	that's your primary plan is, okay, look, it's going to try this, and if it works, great.
2855300	2859620	Well, you have to have a backup plan, right? And in many cases, we had to have another backup to
2859620	2866660	the backup plan because we couldn't fail and make everything stop working. So if anyone in the
2866660	2872980	program failed, we had to have a backup plan for what would happen if they failed, and then a backup
2872980	2880680	plan for if our backup plan failed. And then the last time, the last one, which is a lesson learned
2880680	2887980	is we thought we were prepared in many, many, many occasions. But let's say, you know, in between days
2887980	2893940	of the exercise, when we would pause and go back to our hotels to sleep, etc., I would often make
2893940	2901020	runs to Home Depot or Lowe's or electrician stores or whatever, because no matter how many spare
2901020	2908000	parts we had, no matter what tools we had on us or available to us, anything that can break
2908000	2913220	will break at some point when you're running these environments. And it's almost always
2913220	2918120	in the way that you never thought of or that you couldn't have anticipated. Something that has,
2918120	2924460	you know, a 10,000-hour mean time between failure or 100,000-hour mean time between failure fails in,
2924460	2930600	you know, 10 hours instead. So lots of interesting challenges on just keeping
2930600	2936440	things up and operational and making sure that stuff was readily available if anything did break.
2936940	2940780	So let's talk a little bit about some personal takeaways, and I'll wrap these up really quickly
2940780	2948320	here. But let's talk, let's say, not as the University of Illinois, but let's talk about
2948320	2955520	this from my perspective. So vendors, be this ICS cyber solutions or the vendors themselves,
2955520	2963320	they often claim capabilities that, let's say, are much more limited in the real world application
2963320	2968620	than what most people realize. So a utility may say, I go buy this platform and it's got me
2968620	2974120	covered and it can do all of these things and I can check that box and I'm good. The reality is,
2974760	2982740	no matter what vendors claim, there's often still very large gaps there. And so even the
2982740	2986740	commercial off-the-shelf ICS cyber solutions that are out there, they're missing huge amounts of
2986740	2992900	surface area on what adversaries can do against these boxes. Radix technology was designed to
2992900	2997960	close some of those gaps, but not all of them, right? So even as great as the Radix technology
2997960	3005080	is, we still have a long way to go, right? In building the environments that we built and
3005080	3012640	helping to construct the exercise evaluations and the test effective payloads and all that,
3012640	3016920	in essence, is how do you cause a condition from a cyber means to happen on these devices,
3016920	3023000	such that there are artifacts or implementations that then people can forensically find, right?
3023520	3028840	So all of those, in doing that, we found hundreds of issues on these devices. And it's not like
3028840	3033340	we've never looked at these devices before. And by issues, I don't necessarily mean security
3033340	3039100	vulnerabilities, but in some cases it was security vulnerabilities. But merely other items like,
3039100	3044700	look, compatibility between host A and host B, it doesn't work. Even though they're supposed
3044700	3049500	to interoperate, it doesn't. There's nuances, differences, there's differences in documentation
3049500	3055280	on what is communicated on the actual wire versus what it says it's going to communicate as.
3056200	3064120	Another thing, which was a personal takeaway, is being the adversary is fun, right? It's nice
3064120	3070820	to be on the red team and hack these devices and break them in a variety of ways. But in the
3070820	3075940	program, the defense and recovery technology, including the RADIX technology and commercial
3075940	3083520	off-the-shelf stuff that I've personally seen, it's still way behind what I was capable of or
3083520	3089660	what others on the red team were capable of doing to these systems. So if we're so far ahead,
3089660	3096020	we could just obliterate any of that tech, then what fun is there in that? It's not even a fair
3096020	3101900	fight at that point. So a lot of times we limited the activities that we were doing to poking the
3101900	3107840	bear rather than destroying it. So we didn't go out for the throat kill. We kept a pace with
3107840	3112500	what the technology was capable of and designed something that was just a little bit ahead of that,
3112500	3120820	pushing them each iteration to improve. And so one sort of broad takeaway is,
3120820	3126740	and I say this not just of technology in North America or whatever, but the whole world, what
3126740	3132480	they have in this space in industrial control systems, detecting cyber attacks on these devices,
3132480	3137120	that detection, that mitigation, and that remediation technology for the electric power
3137120	3144860	grid. And I'll stretch it a bit and say actually all critical infrastructure still really has a
3144860	3151280	long way to go. There's still so much work that needs to be put on those platforms to really
3151280	3157160	protect the systems from somebody who is truly focused and determined and understands these
3157160	3164200	systems at a deep and inherent level. So that's all of my technical content. I will just flash
3164380	3169960	a slide real quick, which is the testbed at Illinois and much of what we've built in the
3169960	3176300	RADIX program has been enabled by lots of companies. These are some of the
3176300	3181300	the companies that have donated gear to us, software to us, et cetera, that have helped
3181300	3187680	enable the things that we've done. But without them and without the commercial support and
3187680	3193260	the vendor support and the utility support broadly across this program, we wouldn't be successful.
3193260	3197260	The DARPA RADIX program wouldn't have been successful. So thank you to all of those companies
3197260	3204600	and what they did. And then I think we still have a couple minutes for questions. And so
3204600	3210680	I'll also leave a sort of bonus link down there at the bottom. There's a GitHub repo that I created
3210880	3217740	a number of years ago at the S4 conference, and I've been maintaining it sort of ad hoc
3217740	3223440	ever since. And that's a bunch of ICS security tools in a variety of different forms that are
3223440	3230460	aggregated and categorized in various ways and mirrored when their original location
3230460	3235640	is no longer available. So do check that out. It has a whole bunch of useful things in it.
3235640	3241040	And with that, I will stop talking and I think we might have a little bit of time for question
3241040	3250910	and answer. Let's see. Hey, Tim, this is Bryson. How are you doing? Wonderful. Hi, Bryson.
3251070	3257030	Thank you. Thank you for the talk. I noticed that you are on our Discord and I actually
3257030	3262570	promoted you to a speaker during your talk. So you should now have that badge tied to you.
3262790	3269750	And what we recommend is if you could post that GitHub link in the speaker Q&A
3270550	3278630	section of Discord. Okay. And then reach out for folks to engage you there and for questions.
3278930	3284710	Okay. Sounds good. So really appreciate you jumping on and giving this talk.
3285370	3291730	Having been and seen this for myself, it is really impressive. And my favorite part for
3291730	3298570	the sensors was of course the inflatable guys like you see next to the used car sales. I thought
3298570	3302690	that was a really interesting way to show whether something is up or down at a physical distance.
3302950	3305510	Yeah, we affectionately call them the dancing men.
3307770	3314170	And sort of a funny aside, in the Nor'easters, when you have torrential downpour, those things
3314170	3318950	get wet and then they turn into sort of like whiplashes. So I was up there, you know,
3318950	3325630	untangling them on many occasion and getting sort of smacked by the dancing men as I was trying to
3325630	3330130	untangle them so that they could fly. Well, that's how you know it works.
3332720	3338560	Well, anyway, Tim, I appreciate you joining us and supporting the village and look forward to
3338560	3343700	the commentary and the Q&A on Discord. Awesome. Yeah. And everyone do check out
3343700	3347980	what they've set up for, you know, the CTFs and other things in the village.
3347980	3352540	You know, they do an awesome job of creating environments that you can play with.
3352660	3358160	Sadly, I can't offer my environment out to the world in such an easy and accessible way.
3358200	3362880	But hopefully in the future, I'll get deeper engaged with the ICS village and bring some
3362880	3367680	of this tech and some of this capability to the village so you guys can all play with it too.
3368100	3372380	Yeah, we look forward to that. That's probably been the biggest innovation we've had is because
3372380	3377720	of the pandemic. The amount of effort we've had to spend on figuring out how to make these things
3377720	3383660	virtually accessible, which is the typical limitation for concurrent access. We kind of
3383660	3387740	have solved it. So we'd love to touch base with you afterward and talk about it.
3387800	3392820	Yeah, it's, you know, great to hear that you guys have had to tackle that. We're currently
3392820	3399420	tackling that for the DARPA Radix effort as well. With the last exercise, it will be predominantly
3399420	3406700	remote. And we went from the prior exercise being, you know, network isolated, completely trusted,
3406700	3412200	everyone in a specific zone to, you know, part of this is deployed in the cloud, and everyone
3412200	3419400	is distributed around the country, and all accessing this in a controlled and crazy way,
3419400	3424720	including like streaming body cams that we'll have and all sorts of stuff. So we're on that
3424720	3432060	same roller coaster due to COVID at the moment. Well, we look forward to collaborating. So again,
3432060	3437600	thank you very much, and we'll see you on Discord. Yeah, you guys have a great day. All right, take care.