Hi, thank you for attending our talk.

00:04.040 --> 00:09.800
I wish we were able to see you in person and hope that in the next year that things will get back to normal.

00:09.860 --> 00:20.500
As you can see from the title, the topic is very important because the Internet, the biggest storage of all your funny pictures and memes runs on electricity.

00:20.500 --> 00:33.760
And we are here to talk about internal self-power generation automations, about vulnerabilities that we were able to find, and about what you can do about that.

00:34.120 --> 00:40.700
We are security consultants who have been working with different industrial solutions for many years.

00:40.700 --> 00:51.180
Actually, we have been doing it for so long that we have a long list of contact information of different system integrators and industrial vendors.

00:51.380 --> 01:02.200
So when an asset owner, for instance, a power plant comes to us and asks for a service, we don't just give them information about vulnerabilities that we found.

01:02.200 --> 01:13.440
We closely work with all involved entities, including the vendor, to find together safe and reliable fixes and workarounds.

01:13.780 --> 01:25.720
We work at Kaspersky, and this research is a result of the teamwork, not just of the three of us, but also of Gleb Guritsay, Sergey Andreev, and Sergey Sidorov.

01:27.060 --> 01:36.260
Everything that we are going to discuss today was reported to the respective vendor, I'm talking about Siemens, a long time ago.

01:36.260 --> 01:40.120
But actually, this is not one vendor problem.

01:40.120 --> 01:45.050
You can find similar issues in systems of other vendors as well.

01:45.740 --> 01:54.860
We are going to talk about real vulnerabilities in real power plants out there, and at first glance, it may seem irresponsible.

01:54.860 --> 02:03.400
But if you think about it, for good guys to do such research, it's a challenge.

02:03.400 --> 02:08.280
You will need to have relevant experience.

02:08.280 --> 02:16.260
You will need to have a lot of time, and you, of course, you will need access to the industrial environment.

02:16.260 --> 02:21.480
There is no welcome sign on power plant doors, right?

02:21.980 --> 02:31.500
So for good guys, for penetration testers, for auditors, for power plant separators, it's challenging to get access to all of the things together.

02:31.540 --> 02:42.060
On the other hand, for bad guys, for those bad guys who would be willing and able to attack a power plant, it's their job to do such research.

02:42.060 --> 02:49.140
They have significant investments, they have a lot of time, but they keep their vulnerabilities to themselves for their malicious purposes.

02:49.420 --> 03:01.400
So we assume that those guys already have all this information, and from our side, we would like to share this information with good guys, with you, so you would be able to act upon this.

03:02.540 --> 03:08.620
Power plants is the main source of electricity on our planet.

03:08.620 --> 03:23.540
And thanks to carbon monitoring, anyone with internet access can get information about where different power plants are located on the world map, what fuel they use, and which is their capacity.

03:24.120 --> 03:27.600
The heart of every power plant is a turbine.

03:27.600 --> 03:34.260
We don't have a picture of a turbine here, but if you ever saw a modern airplane, I believe you also saw a turbine.

03:34.260 --> 03:37.700
This is a giant rotating thing generating electricity.

03:39.240 --> 03:43.440
And on power plants, they look and work quite similarly.

03:46.680 --> 03:53.380
Turbine manufacturers are generous enough to share information where the turbines are used.

03:53.380 --> 03:57.700
Here, for example, a screenshot from Siemens' website.

03:58.720 --> 04:07.340
Turbines are used not only on power plants, they are used in many different areas like chemical or oil and gas and many others.

04:07.340 --> 04:16.560
But if you correlate this picture with the previous one, you will be able to understand a solution from which vendor is used on a particular power plant.

04:17.400 --> 04:29.520
In addition to that, online you can find a lot of information about what solutions are used in certain power plants, in different press releases and marketing materials.

04:29.520 --> 04:36.720
You can find a lot of interesting information about software hardware version generations or different systems.

04:37.060 --> 04:39.740
Sometimes you can even find building plans.

04:39.740 --> 04:41.780
Here's just a small example.

04:41.780 --> 04:44.700
Okay, Google, show me some power plants of California.

04:45.820 --> 04:49.600
Here are just a few power plants of California.

04:49.600 --> 04:53.000
And they have one more thing in common.

04:53.120 --> 04:58.260
They use the same plant control system, SPPAT 3000 from Siemens.

04:58.260 --> 05:04.020
This is exactly the system that we are going to discuss today.

05:04.400 --> 05:16.500
But before we move on to power plant generation automation, let's talk a little bit about power generation process in general, what we are going to automate.

05:18.900 --> 05:32.300
Here and throughout the presentation, we will be intentionally oversimplifying a lot of things, partially to make them more suitable for the audience and partially because, to be honest, we don't fully understand them ourselves.

05:32.840 --> 05:35.700
So let's go from right to left.

05:37.280 --> 05:39.040
First, you will need some fuel.

05:39.040 --> 05:41.220
Here is coal, for example.

05:41.220 --> 05:49.280
You put fuel into a combustion chamber, put it on fire, and it generates pressure to rotate a turbine.

05:49.320 --> 05:58.080
The turbine is connected to an electricity generator through a shaft, so when it's rotating, the generator starts generating electricity.

05:58.280 --> 06:04.140
But it's important to mention that electricity doesn't go straight to your house or city.

06:04.440 --> 06:08.620
First, it goes to a special place called power grid.

06:08.620 --> 06:20.320
Power grid knows information about market demands, it receives energy from different power plants, and this is power grid who distributes electricity to consumers.

06:21.160 --> 06:31.400
During the burning process in the combustion chamber, you can have a lot of excessive heat, so-called cold waste heat, and there are different ways how to approach it.

06:31.400 --> 06:38.300
First, you can release it to the air through a condensing tower, or you can reuse it during recuperation.

06:38.800 --> 06:45.860
For example, warm water and send the steam to a turbine to generate more electricity.

06:47.480 --> 06:55.120
Systems that are used to automate this process are called distributed control systems, or DCS.

06:56.420 --> 07:02.140
They are designed to make life of power plant operators much, much easier.

07:02.240 --> 07:07.140
They allow you to conveniently start and stop the power generation process.

07:07.140 --> 07:15.660
They allow you to control the amount of electricity you want to generate, you just enter there the amount in megawatts that you want to have at the output.

07:15.660 --> 07:18.080
And they allow you to monitor everything.

07:18.080 --> 07:21.760
These systems are literally very powerful.

07:21.940 --> 07:29.620
They are connected through PLCs, they're connected to many parts of the plant, including the turbine.

07:29.620 --> 07:46.960
And they control such interesting things as the amount of fuel, the temperature in the combustion chamber, the rotation speed of the turbine, and even control the turbine not to go into different dangerous modes.

07:46.960 --> 07:53.280
Obviously, it's not a small piece of software that you just install on the server and it magically works.

07:53.280 --> 08:05.160
It's a very sophisticated system consisting of different hardware, software, PLCs, input-output modules, the turbine itself, and a lot, a lot of things.

08:05.480 --> 08:10.660
And often starting to create such a system starts even from building a structure.

08:10.660 --> 08:17.640
So someone comes to a vendor and says, we have an empty field, please build us a power plant.

08:17.820 --> 08:24.080
And there are many vendors who do this, but today we will be talking about Siemens.

08:26.020 --> 08:31.220
The DCS from Siemens that we analyzed is called SPPAT3000.

08:31.220 --> 08:45.220
Just like other DCSs, it consists of many different industrial components, PLCs, OPCs, different servers, HMI, a lot of things.

08:45.220 --> 08:55.680
And it may have very different architecture depending on the site, but there will be two components that are unique for SPPAT3000.

08:55.680 --> 08:58.800
They are called application server and automation server.

08:58.800 --> 09:01.140
And this is how we will structure our talk.

09:01.140 --> 09:08.820
First, we will talk about application server, then we will move on to automation server, and then we will move on to conclusions.

09:09.860 --> 09:18.760
In different manuals and documentation from Siemens, you will see how the system should be built in a perfect world.

09:18.760 --> 09:30.000
For example, they will say that the application network where application server is located should never be connected to any external networks, and how everything should be designed.

09:30.840 --> 09:37.920
However, also, we again here worry over simplifying everything.

09:39.040 --> 09:46.320
In reality, in real power plants, you will meet a lot of interconnections to other systems.

09:46.320 --> 09:52.580
For example, you will need a sensor network to monitor different vibrations inside the turbine.

09:52.980 --> 10:01.320
You will need a demilitarized zone because you will need to get some kind of remote support from the vendor.

10:01.320 --> 10:06.260
You will need to get updates for your operating systems, for antivirus, and so on.

10:06.260 --> 10:14.460
You will need to push out OPC traffic to your corporate network or to a regulator because this area is very strictly regulated.

10:14.460 --> 10:19.040
So, in practice, you will need a lot of interconnections.

10:20.280 --> 10:26.120
The life of our vulnerabilities started almost two years ago.

10:26.120 --> 10:45.860
Back in November 2018, we reported a bunch of vulnerabilities to Siemens, and about a year later, Siemens published an advisory containing information about how to approach these vulnerabilities, and also a set of other vulnerabilities that were reported by other vendors,

10:45.860 --> 10:52.140
other teams, and that's great that this area receives a lot of attention from security researchers.

10:52.820 --> 10:59.820
But also, about a year passed, it doesn't mean that during this year, Siemens didn't do anything.

11:00.600 --> 11:05.740
The thing is, SPPK3000 is an exclusively supported system.

11:05.740 --> 11:11.120
It means that a system integrator for this is Siemens themselves.

11:11.120 --> 11:22.900
So, soon after we reported these vulnerabilities, Siemens started to roll out patches and working directly with their clients to fix everything.

11:23.140 --> 11:26.180
So, December is just when this information became public.

11:28.160 --> 11:35.880
We don't have a lot of time to discuss in detail what kind of attacker, what can do with the system.

11:35.880 --> 11:48.140
I will just highlight that CVSS scores given here, obviously, do not represent how critical these vulnerabilities for real power generation process.

11:48.140 --> 11:53.840
They're just individual scores for vulnerabilities in the vacuum.

11:53.840 --> 12:04.140
To better understand what kind of attacker can do what, you can take a look at our threat model that is published in our white paper.

12:06.440 --> 12:10.120
Let's start with application server.

12:10.120 --> 12:14.960
Application server is a logical core of the entire system.

12:14.960 --> 12:21.100
Everything has connections to application servers in the logical sense.

12:21.240 --> 12:25.860
If anything needs to connect to the network, it will end up in application server.

12:25.860 --> 12:31.420
Other servers start their work from the loading software from application server and launching it.

12:31.420 --> 12:33.880
So, this is the heart of the system.

12:33.880 --> 12:38.960
And what can possibly go wrong if you open over 40 ports there?

12:39.540 --> 12:42.040
This is for an attacker.

12:42.040 --> 12:44.260
This is a huge attack surface.

12:44.980 --> 12:47.960
They are likely to get into their respective network.

12:47.960 --> 12:50.080
They can choose what they want to attack.

12:50.080 --> 12:55.040
Do they want to attack Windows operating system because this is simply a Windows server?

12:55.040 --> 12:57.200
Do they want to attack third-party components?

12:57.200 --> 13:02.800
Or they want to attack own SPP 83,000 services which are based on Java?

13:04.820 --> 13:08.460
Also, we hope that these vulnerabilities are already fixed.

13:09.180 --> 13:14.740
In industrial environment, usually, you don't update your systems very often.

13:14.740 --> 13:21.720
Usually, it's about half of a year or several months between major updates of operating system.

13:21.720 --> 13:33.560
So, it's always possible to find a time window with remotely exploitable vulnerabilities in Windows operating system.

13:33.560 --> 13:35.260
Configurations also could be better.

13:35.260 --> 13:39.480
You can find some statistics for security benchmarks on the right-hand side.

13:40.100 --> 13:44.020
But one of the biggest problems is actually passwords.

13:44.380 --> 13:49.620
The life of passwords has three stages.

13:49.620 --> 13:52.800
At first, passwords were the same for all power plants.

13:52.800 --> 13:54.860
They were default and the same everywhere.

13:54.860 --> 13:56.900
And you can find them online.

13:57.380 --> 14:01.720
Obviously, this screenshot were not from information published from Siemens.

14:01.720 --> 14:10.840
Some power plant operators decided that it would be a good idea to share passwords and a lot of other technical information with the Internet.

14:11.560 --> 14:19.360
But they are available online and we also have a work list in our white paper.

14:20.140 --> 14:27.280
Around 2014-2015, Siemens started to generate different passwords for different applications.

14:27.280 --> 14:30.740
However, the process of changing them was challenging.

14:30.740 --> 14:35.240
You would have to be familiar with the process to change the passwords by yourself.

14:35.280 --> 14:44.540
And only in the last year, in 2019, the process became easier and now you can do it yourself much easier.

14:44.560 --> 14:50.520
Now please welcome Radu who will tell you about vulnerabilities in Java.

14:52.040 --> 14:53.680
Hello everyone.

15:07.810 --> 15:12.730
Let's look how SPP software works on application server side.

15:12.830 --> 15:17.570
Operator can communicate with system through theme or fed client.

15:17.570 --> 15:29.090
In case of theme client, it uses Java plate of Internet Explorer and communicates with server over HTTPS.

15:29.090 --> 15:36.530
So it can be outside of application network and its communication can be constrained by firewall.

15:36.530 --> 15:42.770
In opposite, in case of fed client, operator should belong to application network.

15:42.770 --> 15:58.110
And fed client directly communicates with RMI registry to found RMI services and after that directly communicates with Sys services.

16:06.640 --> 16:12.080
Illustration of SPP architecture was kindly provided by system through a public URL.

16:12.080 --> 16:16.160
So not to be missed, let's divide it into spaces.

16:16.540 --> 16:22.100
In red zone there are items that process HTTPS requests.

16:22.100 --> 16:26.080
And in green zone there are RMI services.

16:26.080 --> 16:32.300
RMI service looks like network services which assert on dynamic TCP ports.

16:32.780 --> 16:36.360
SPP consists of containers.

16:36.860 --> 16:41.100
All types of containers are represented on these illustrations.

16:41.100 --> 16:47.060
And containers have self-explanatory names.

16:47.060 --> 16:55.540
So before we go deep inside internals of SPP, let me introduce some tools which used in this research.

16:55.540 --> 17:02.320
First of all, all jars files of SPP are obfuscated with commercial product.

17:02.320 --> 17:06.860
But this security measure can simply bypassed by public available tool.

17:06.860 --> 17:12.220
Secondly, sometimes it is useful to see how legit software communicates with server.

17:12.220 --> 17:18.040
It helps to understand architecture and to see client workflow.

17:18.520 --> 17:22.100
In case of SPP, RMI desector was written.

17:22.100 --> 17:27.000
It represents raw TCP streams and in human readable format.

17:27.000 --> 17:31.640
Inside it used read object method of SDK.

17:31.640 --> 17:38.900
It is known that this method suffers from insecure deserialization vulnerability.

17:39.180 --> 17:43.440
So be sure not to be exploited through remote pickup.

17:45.620 --> 17:49.560
The first pillar of SPP is Apache web server.

17:49.560 --> 17:56.360
According to its configuration, folder Orion Software Config can be accessed by unauthorized user.

17:56.360 --> 18:07.660
But in fact, this folder contains some critical information about application and about items of application and automation network.

18:07.660 --> 18:14.860
Also, configuration of Orion web application in Tomcat also can be accessed.

18:16.020 --> 18:21.400
Tomcat, there are three web applications registered in Tomcat.

18:28.010 --> 18:33.230
There are Remote Diagnostic Service, Manager and Orion.

18:33.290 --> 18:44.090
According to configurations of Apache and Tomcat, all these applications can be accessed by unauthorized user.

18:45.090 --> 18:50.230
Inside Orion web application there are seralettes which can be accessed.

18:50.230 --> 18:57.460
All of them are listed in configuration web.xml and the list is huge.

18:57.790 --> 19:04.150
Some of seralettes has attractive names for attacker.

19:05.150 --> 19:17.130
For example, BrowseSeralette allows unauthorized user perform directory listing on arbitrary folder.

19:17.130 --> 19:22.490
But in case of exploitation, another seralette is more useful.

19:24.650 --> 19:42.980
FileUploadSeralette allows unauthorized user perform file upload and folder is fully controlled by parameters based on target name of HTTP request.

19:43.150 --> 19:48.680
This vulnerability can simply be bypassed to remote code execution.

19:50.820 --> 20:08.120
For example, attacker can corrupt some startup scripts of SPPoA or simply inject JSP Shell in Tomcat web application and get remote code execution with system rights.

20:13.140 --> 20:17.280
Also there are seralettes which has service factory in its name.

20:17.280 --> 20:22.560
This seralette redirects HTTP request to RMI services.

20:22.800 --> 20:46.220
Inside it uses parameter service url of HTTP to identify RMI service which will be called and serialized object in data section of HTTP request contains information about method and arguments which will be called.

20:47.260 --> 20:58.300
So there are situations when themed client and fan client can communicate with RMI services.

20:58.300 --> 21:08.780
But in case of fed client, it can communicate with RMI registry.

21:08.780 --> 21:29.960
So if application server miss some important security updates of Java, then server contains insecure deserialization vulnerability and public available tool ySourceSerial can exploit it and perform remote code execution with system rights on server.

21:29.960 --> 21:43.800
So the next task will be to identify all input vectors for attacker and for this task we will try to list all RMI services in system.

21:43.800 --> 21:51.240
At first step we will use class LocateRegistryOffice.com and get big list of RMI services.

21:51.240 --> 22:02.840
All but one are Jamex RMI services and I assume that they used to control and manage containers of spp.

22:02.840 --> 22:08.860
For further investigation we will choose Lockup service.

22:08.860 --> 22:23.020
In fact, it looks like a collection of next level RMI services and using its public methods we can get the reference to this next level RMI services.

22:23.340 --> 22:29.920
Next level RMI services should implement InterfaceServiceFactory.

22:30.920 --> 22:51.720
So it also looks like some collections of another next level RMI services and using public methods getService and parameters such as clientId and name of the service.

22:51.720 --> 22:59.900
The instance of next level RMI service will be created and reference to it will be returned to client.

23:01.700 --> 23:11.880
And this next level RMI service is a server which performs real job of spp.

23:11.880 --> 23:22.380
But in fact it contains a lot of public methods which can be accessed by unauthorized user.

23:22.800 --> 23:28.340
So input vector of spp is very huge.

23:28.340 --> 23:35.760
The next question is to understand how authentication performs on a system.

23:35.760 --> 23:43.470
For this task let's look how client performs request to security service.

23:44.760 --> 23:56.060
To do this first of all client tries to get reference on security service with some clientId.

23:56.060 --> 24:02.420
It needs to PCServiceFactory use this clientId to get valid session in SessionManager.

24:02.420 --> 24:11.560
If SessionManager will fail then exception will thrown and client request will be rejected.

24:11.560 --> 24:18.900
But in case of success valid sessionId will be returned to PCServiceFactory.

24:18.900 --> 24:34.220
And in its turn PCServiceFactory create instance of security service where sessionId will start in loginId.

24:34.700 --> 24:39.240
And reference to this instance will be returned to client.

24:39.240 --> 24:45.420
Further client can call some public methods of this service.

24:46.900 --> 24:55.180
And in its turn these methods can perform some privileges checks of client.

24:55.240 --> 24:59.600
So we have two security measures of system.

25:00.180 --> 25:08.300
But there is a question how client can perform login operation on system if he doesn't have any valid clientId.

25:08.300 --> 25:18.340
For this task at startup of SVPR SessionManager create anonymous session with clientId 0.

25:18.460 --> 25:24.380
And client use this clientId and perform login operation.

25:24.380 --> 25:30.500
But attacker can also use this and simply bypass this security measure.

25:30.500 --> 25:44.780
To sum up, there are a lot of RMI services which has a lot of public methods.

25:45.240 --> 25:50.440
And permissions checks are fully delegated to these methods.

25:50.440 --> 25:56.840
So it's really difficult to perform security management of this system.

25:57.920 --> 26:03.360
So we understand all input vectors and security measures.

26:04.200 --> 26:08.190
So it's time to find vulnerabilities.

26:08.800 --> 26:13.800
In the list of RMI services there is admin service.

26:13.800 --> 26:16.680
It can be accessed by an authorized user.

26:16.680 --> 26:21.340
And its public method transcript doesn't have any privileges checks.

26:21.340 --> 26:30.680
In fact inside it first step create instance of class loader using bytes from arguments.

26:31.500 --> 26:36.540
In fact this step will load arbitrary Java class.

26:37.280 --> 26:43.160
This class should implement interface admin script and defined method execute.

26:43.160 --> 26:48.460
This method will be called by run script of RMI services.

26:48.460 --> 26:58.620
For this case we create Java class which simply run OS command.

26:58.920 --> 27:02.920
And this OS command will be run with system rights.

27:03.340 --> 27:13.840
In fact there is more powerful post exploitation because we inject arbitrary Java class around SPPS software.

27:13.840 --> 27:22.740
So we can use some Java reflection and patch some private variables of SPPS.

27:22.740 --> 27:32.320
And as a result we can corrupt some technological process of SPPS.

27:33.400 --> 27:42.340
To bypass privileges checks in methods we can use second vulnerability.

27:51.020 --> 27:58.800
It's using RMI session service and its public method get login sessions.

27:58.800 --> 28:05.640
Attacker can get information about all login user on the system.

28:05.640 --> 28:13.820
This information contains user names, IP and client ID of login users.

28:13.820 --> 28:42.660
Attacker can reuse this and if in this information there is a user with admin rights then attacker can simply reuse his client ID and get the reference to security service with more privileged session.

28:43.020 --> 28:57.580
And after that attacker can call public method get all users of security service and as a result get all private information about all users on system.

28:57.580 --> 29:02.740
Moreover password hashes also contains in this information.

29:04.900 --> 29:15.760
Both of these vulnerabilities can be accessed from either external or application network.

29:15.760 --> 29:25.700
All communications between RMI services are unencrypted so username and password hashes are transferred in plain text.

29:25.700 --> 29:31.820
Moreover system doesn't have any session protection mechanism.

29:32.060 --> 29:48.760
This fact is more critical in case of fed clients because of attacker can perform meat attack on the user of SPPS and get valid username and password hashes from the traffic of user.

29:48.760 --> 29:59.960
And after that simply reuse this username and password hashes and perform login operation on the system.

29:59.960 --> 30:07.940
Moreover attacker can also change the password of the user.

30:08.220 --> 30:15.740
I talked a lot about password hashes and users so it's time to understand how these items are organized on the system.

30:15.740 --> 30:17.220
Alex, you're welcome.

30:19.960 --> 30:21.580
Hello everyone.

30:21.580 --> 30:24.540
Let's continue our discussion about application server.

30:24.600 --> 30:28.420
On the previous slide you could see how remote authentication works.

30:28.420 --> 30:31.400
Now I'm going to tell you about how it's organized locally.

30:31.440 --> 30:42.180
After the system gets started it begins to read the content of files users1.xml and pdate1.xm to get user list and their password hashes.

30:42.180 --> 30:48.400
User1 is a simple XML while pdate1 has a slightly more complex structure.

30:48.400 --> 30:51.300
It's a gzip archive encoded in base64.

30:51.300 --> 30:58.200
There is a javascriptization object in the gzip archive containing a specific XML.

30:58.200 --> 31:03.020
The fields of this XML from pdate1 file are presented on the slide.

31:03.020 --> 31:09.490
They are used to calculate password hashes and check it during user authentication.

31:09.490 --> 31:16.930
At the bottom of the slide you can see a password check algorithm in a pseudocode.

31:16.930 --> 31:21.930
The cryptographic scheme is a typical crypt hashing scheme like in your Unix and Linux machines.

31:21.930 --> 31:29.210
It has solved different number of iterations and the only one thing which was added is hardcoded salt.

31:29.210 --> 31:34.530
The same for all users which is concatenated to the password.

31:35.670 --> 31:42.370
The tool to extract password hashes and their parameters from pdate1 file has been developed.

31:42.370 --> 31:45.370
Its output is presented on the slide.

31:45.750 --> 31:54.110
The tool can be used during password auditing to check weak or dictionary passwords and their hash calculation parameters.

31:54.110 --> 31:59.510
The tool is available in our GitHub repository.

32:00.650 --> 32:03.450
Draw the line under application server analysis.

32:03.450 --> 32:12.110
As you have seen, the attack surface is really huge and includes Java and MySQL systems, Tomcat applications and a lot of others.

32:12.270 --> 32:16.170
Secondly, it's about remote connections.

32:16.670 --> 32:24.250
Whether SPP has or has not remote connections according to vendor, system integrator or someone else, you should check it.

32:24.250 --> 32:28.630
And the good starting point for this is application server.

32:28.630 --> 32:37.530
Because OPC maintains remote operator, all of these things will end up on application server.

32:37.530 --> 32:50.170
Thirdly, despite the fact that there is automation network between application server and field devices, an attacker can affect generation process from application server.

32:50.170 --> 32:59.530
These actions include to start stop generation, change power output or just get information how power plant works.

33:01.370 --> 33:09.250
Of course, such manipulation will always be visible for operator, always monitoring technological process.

33:09.250 --> 33:17.690
So a real attacker will also be required to change or modify data on operator's HMIs.

33:17.690 --> 33:21.690
But it's also possible with real security issues.

33:22.470 --> 33:24.910
That's all about application server.

33:24.910 --> 33:31.930
Now let's move on to another main component of SPP infrastructure, automation server.

33:34.070 --> 33:42.870
The main goal of the automation server is to execute real-time automation functions and tasks for power plant control.

33:43.830 --> 33:55.050
Depending on power plant project architecture and features, the role of the automation server can be different.

33:55.050 --> 33:57.130
We have distinguished three roles.

33:57.130 --> 33:59.130
And the first one is automation.

33:59.510 --> 34:17.310
There may be slight confusion because the term automation is used both for server and its role, but analyzing automation server configuration and publicly available information about it, we have found that whatever the role is, almost the same hardware and part of software are used.

34:17.310 --> 34:23.170
So we have decided to use this kind of role classification, which seems less confusing to us.

34:23.170 --> 34:28.570
But at the same time, it's slightly different from the vendor's one.

34:28.570 --> 34:41.850
Anyway, having an automation role means that the server is responsible for interaction with input-output modules, which control and monitor power plant equipment such as turbines or electric generator.

34:42.130 --> 34:44.870
The second role is communication.

34:44.870 --> 34:49.810
This role is used to communicate with third-party systems.

34:49.810 --> 34:59.830
In another words, it's just a protocol converter, supporting such protocols as Modbus, IEC 101, 104, and some others.

35:00.090 --> 35:01.990
And the last role is migration.

35:02.730 --> 35:13.450
In this role, the server is used to connect previous versions of SPPA, such as SPPA-T2000 or Teleperm-ME.

35:13.450 --> 35:21.530
In the automation role, the automation server can be run both on schematic-assigned PLCs or industrial PCs.

35:21.530 --> 35:26.210
In the case of other roles, it can be run only on industrial PCs.

35:27.630 --> 35:36.390
Let's talk a little more about each role and let's start with the automation role based on PLCs.

35:36.430 --> 35:42.870
PLCs are what directly control field devices and access to them is game over for any security discussion.

35:42.870 --> 35:50.670
Any configuration changes and updates for PLC are required to stop technological process.

35:50.670 --> 36:00.070
Therefore, these devices usually have security misconfiguration and firmware without security updates.

36:00.090 --> 36:08.850
Another common security issue for PLCs is using unsecure industrial protocols.

36:08.850 --> 36:15.870
In the case of SPPA, there are schematic S7 protocol and PLC data protocol.

36:17.010 --> 36:23.010
There is quite a lot of information about S7, but not so much about PLC data protocol.

36:23.010 --> 36:26.510
So we had to deal with it and analyze it ourselves.

36:26.870 --> 36:29.330
It's not a special protocol for SPPA.

36:29.330 --> 36:37.730
When you program your PLCs and you need to exchange some data between them in real time, you use this protocol.

36:37.730 --> 36:45.210
It's pretty simple and maybe its description is available somewhere in the internet, but we couldn't find it.

36:45.210 --> 36:47.950
So just in case, I'll show its structure here.

36:48.510 --> 37:02.550
It doesn't have any security mechanism and the only obstacle while dooming in the middle attack to spoof data is a sequence number, which we can get from a packet and just a fuzz incrementation.

37:04.050 --> 37:10.790
For protocol analysis, Wireshark Dissector has been developed and is also available in our repository.

37:12.050 --> 37:23.790
During PLC security assessment, one of the main things which we check is unauthorized access to reading and writing the PLC memory.

37:23.790 --> 37:36.150
Availability of unauthorized access is determined by the position of mode selector of schematic PLCs and some other configuration parameters.

37:36.470 --> 37:45.230
The matrix on the slide shows unsecure states for schematic PLCs when unauthorized access is possible.

37:46.390 --> 37:58.310
The tool for gathering information from PLCs over the network and for its analysis has been developed by one of our colleagues and also available in our repository.

38:01.800 --> 38:06.440
Now let's talk about automation server based on industrial PC.

38:06.440 --> 38:11.520
The workflow of all roles in this case is quite similar to each other.

38:12.360 --> 38:17.880
When automation server is based on industrial PC, it's just a Linux box.

38:17.880 --> 38:23.740
During the start, it tries to download some additional files from application server.

38:23.740 --> 38:36.560
These files include JARs, which represent SPPA runtime containers, Barscript, some configuration files, and other.

38:36.560 --> 38:43.020
In order to execute downloaded JARs, PTC PERC virtual machine is used.

38:43.020 --> 38:51.920
It's a real-time Java virtual machine widely spread in industrial and military areas.

38:53.280 --> 39:01.600
After that, running JARs open RMI services or some of their extension.

39:01.600 --> 39:08.180
In case of migration server, Orion RPC services, which are extension of classic Java RMI services, are used.

39:08.180 --> 39:11.780
And you can see their listing on the slide.

39:13.260 --> 39:19.400
Automation server based on industrial PC has following security issues.

39:19.400 --> 39:27.600
Firstly, there is a possibility to spoof downloaded from application server files.

39:30.360 --> 39:39.080
These files are downloaded over HTTP and there are no security mechanism like authentication or integrity check during this process.

39:39.080 --> 39:42.120
Secondly, it's about using default credentials.

39:42.120 --> 39:44.600
Username admin with password cm.

39:44.640 --> 39:48.680
Thirdly, it's RMI services running on automation server.

39:48.680 --> 39:57.980
The research has found two vulnerabilities in Orion RPC services, which allow to perform sensitive data exposure and RCE.

39:57.980 --> 40:05.820
And the last group is vulnerabilities found in the software used to fulfill

40:09.300 --> 40:12.460
a migration role for connection previous version of SPPA.

40:13.540 --> 40:18.000
SPPA-T2000, also known as TXP.

40:21.020 --> 40:33.880
All these vulnerabilities found in migration server software are related to different kinds of overflow, stack, heap, integer, and other.

40:33.880 --> 40:47.300
Actually, there are so many overflows here that this talk would be overflown by that if we started to describe all these vulnerabilities in details.

40:48.580 --> 40:58.530
If you want to know about RPC vulnerabilities, these vulnerabilities have been found in runtime engineering service.

40:59.740 --> 41:11.440
This service has a method, requestRuntimeContainer, where the first argument defines an action to be executed.

41:11.440 --> 41:16.320
Using the action readFile, it's possible to read any file from the system.

41:16.320 --> 41:23.200
Using writeConfigFile action, it's possible to write any file to any folder in the system.

41:23.260 --> 41:32.380
For example, it can be jar file, which executes shell command from the command line.

41:32.380 --> 41:43.400
Then, using the same requestRuntimeContainer method, it's possible to execute this jar later.

41:44.640 --> 41:47.060
That's all about automation server.

41:47.060 --> 41:53.260
To sum up, automation server can be run on PLC or industrial PC.

41:53.260 --> 41:59.420
In case of PLC, it's a usual PLC with well-known security issues.

41:59.420 --> 42:11.500
In case of industrial PC, it's a Linux box, which tries to download jars from application server and then executes them with PHP or virtual machine.

42:11.500 --> 42:20.580
An attacker can spoof downloaded files or just exploit revealed vulnerabilities in network services.

42:22.140 --> 42:30.820
So far, I haven't mentioned any network equipment used in distributed control systems.

42:31.180 --> 42:37.280
During the research, we saw a wide variety of network devices and network infrastructure.

42:37.280 --> 42:46.760
They include different kinds of switches, routers, firewalls, and more rare devices, such as data diet, for example.

42:46.760 --> 42:55.740
We tried to summarize all this information and got common SPP network topology scheme presented on the slide.

42:57.520 --> 43:13.000
We have shown in purple usual places for network devices, but it also should be mentioned that the same devices in the same places can be found in other distributed control systems from other vendors.

43:14.720 --> 43:21.100
Network devices in industrial network usually have a lot of security issues.

43:21.100 --> 43:29.760
The reason is these devices don't require any configuration and can be run out of the box.

43:29.760 --> 43:45.180
Therefore, the things like weak community strings in SNMP, weak credentials in HTTP, FTP, Telnet, and other services, firmware with publicly available exploits, and just security misconfiguration.

43:45.480 --> 43:49.820
All these things are common and typical for industrial network devices.

43:49.820 --> 44:00.960
Additionally, some industrial protocols, for example, such as Profinet-DCP, can allow to get or set network configuration of these devices.

44:01.100 --> 44:13.260
In case of Profinet-DCP, it also can be very useful for device enumeration.

44:13.260 --> 44:32.300
And the last thing about industrial network devices is always remember that these devices with years of uptime can act unpredictably for completely legal and normal activities, such as browsing a webpage with statistics or logging into Telnet.

44:32.620 --> 44:37.460
Here, my part is over, and now Evgenia will sum up our speech.

44:37.460 --> 44:38.360
Thank you.

44:38.880 --> 44:40.680
Thank you, Alex.

44:40.680 --> 44:47.660
So, the topic of power plants is huge, and the topic of DTS is huge.

44:47.660 --> 45:09.400
We just tried to poke a couple of things here and there, and showed that to affect the power generation process, you don't have to go deep to the field level, to PLCs, but you can focus on higher logical levels, like application server and automation server.

45:09.400 --> 45:16.360
What we do not talk about today is havoc or damage that you can cause by such attacks.

45:16.360 --> 45:18.940
Actually, that's because it's not that bad.

45:18.940 --> 45:33.700
If you already imagine a hacker in a hoodie who writes a couple of lines, and after that, the entire city goes into the darkness, it's not like that, because it's power grid who is responsible for power distribution.

45:33.700 --> 45:36.500
This is not a power plant.

45:37.170 --> 45:46.500
So here we mostly talk about more local damage, like would it be possible to damage a turbine.

45:46.500 --> 46:11.460
Since a turbine is connected to a DCS through PLCs, and the turbine is a giant mechanical monster, and it self-degrades by working, probably by putting it into different uncomfortable modes or quickly starting and stopping it, it would be possible to make it degrade even faster or even break it.

46:12.240 --> 46:14.220
We were not able to check it.

46:14.220 --> 46:20.560
Unfortunately, or actually, fortunately, we were not able to find a spare turbine on eBay.

46:20.780 --> 46:29.120
But we are making an educated guess that the damage is out there based on the system architecture.

46:30.060 --> 46:46.460
We wanted to make life of power plants a little bit easier, and we prepared a small do-it-your-own assessment guide that you can use to check your SPPAT3000 system for vulnerabilities that we will discuss today.

46:47.860 --> 46:55.240
You just connect your laptop to a couple of places in the network, go through a simple checklist.

46:55.240 --> 46:59.600
You don't have to hire expensive security consultants for that.

46:59.600 --> 47:10.340
And after that, you can fix some parts yourself, or you can call your system integrators to discuss what to do further.

47:11.740 --> 47:15.660
Just any other industrial system.

47:16.120 --> 47:19.760
DCSs are not so good in terms of security.

47:19.760 --> 47:21.240
It could be better.

47:21.240 --> 47:50.260
And we recommend you to take a look at ISAIC 62443 set of standards to know what to do to improve security in terms of communicating with different entities, because in the industrial area, it's usually a challenge when you, for example, when a vendor is not interested in fixing something.

47:50.260 --> 48:02.440
So it describes in particular what kind of relationships you can build with regulators, with vendors, and other parties involved in the industrial area.

48:03.200 --> 48:11.980
Of course, update your systems, change your passwords, improve your configurations according to the vendor security guidelines.

48:11.980 --> 48:21.800
We also recommend you to set up monitoring since most servers are based on standard Windows and Linux boxes.

48:22.440 --> 48:30.800
You will not be able to detect different Java attacks, but at least you will be able to detect some parts of attacks.

48:31.060 --> 48:41.720
And again, this is more about DCS and industrial security in general, rather than by one system by a single vendor.

48:42.520 --> 48:45.940
We released a lot of information.

48:45.940 --> 48:50.080
We released a white paper, different tools that we mentioned today.

48:50.160 --> 48:55.580
I recommend you to take a look at our GitHub page to find all of that.

48:55.580 --> 49:03.020
And we would like to thank Siemens product search, who made all the communications very effective.

49:03.020 --> 49:04.560
They were very responsive.

49:04.560 --> 49:07.540
They allowed us to contact Siemens product team.

49:07.540 --> 49:12.700
And of course, they released the patch.

49:13.240 --> 49:24.900
Take a look at the advisory and Siemens always tries to raise awareness of their users, how to better build such systems.

49:24.900 --> 49:35.680
What are better configurations, but they also highlight that it's not the vendor who is solely responsible for security of an industrial environment.

49:35.680 --> 49:43.640
There are a lot of things that power plant separators can and must do themselves.

49:43.680 --> 49:47.480
So please follow the guidelines for that.

49:48.260 --> 49:51.180
That's all for our talk.

49:51.220 --> 49:55.680
Thank you very much for your attention and we will be glad to answer any questions.
