WEBVTT

00:00.000 --> 00:01.500
So I guess we'll get started here.

00:01.500 --> 00:02.600
Can you hear me okay?

00:02.600 --> 00:03.780
Is the audio working?

00:03.780 --> 00:04.660
Perfect.

00:05.320 --> 00:19.000
So today we're going to talk about Common Industrial Protocol and just kind of an introduction how to get started if you want to do your own exploitation, maybe learning about the protocol, do some basic pen testing, that kind of thing.

00:20.780 --> 00:23.880
So let's talk about what is CIP.

00:25.740 --> 00:33.900
Common Industrial Protocol is a communications protocol used by industrial devices.

00:34.440 --> 00:37.460
So you have things like programmable logic controllers.

00:37.460 --> 00:42.020
These are the computers actually in your industrial facilities.

00:42.020 --> 00:43.840
They're controlling your plant.

00:43.840 --> 00:51.060
They're running the logic, opening and closing valves, turning pumps on and off, looking at sensors.

00:51.060 --> 01:00.560
And a lot of PLC systems can communicate via CIP or they work with other devices in your plant that will use CIP.

01:00.560 --> 01:09.760
So examples would be like variable frequency drives, which are the devices that control the speed of motors running in your plant.

01:10.020 --> 01:11.640
You have things like motor starters.

01:11.640 --> 01:20.280
These would be energizing motors, power monitoring systems, smart sensors and instruments, devices that open and close valves.

01:20.280 --> 01:26.040
All of these devices can talk Common Industrial Protocol at one level or another.

01:26.820 --> 01:34.500
Now with that, CIP isn't a typical protocol in the sense that we think of for network protocols.

01:34.500 --> 01:38.520
It actually extends beyond your Ethernet networks in your plant.

01:39.140 --> 01:42.960
So there is versions of CIP like DeviceNet.

01:42.960 --> 01:46.420
DeviceNet uses a CAN bus based system.

01:46.420 --> 01:50.340
There's ControlNet, which is coaxial based.

01:50.520 --> 01:52.680
EtherNet IP, which is the Ethernet version.

01:53.060 --> 01:55.660
And CompoNet, which we're not going to talk about because nobody cares.

01:58.220 --> 02:06.820
So originally, it was developed by Allen Bradley, which is a company that builds a lot of industrial hardware, especially in the US.

02:06.980 --> 02:13.260
The very first implementation of it was revealed in Chicago in 1994.

02:13.260 --> 02:19.940
And it really opened up the world for what was possible bringing data onto the plant floor.

02:19.940 --> 02:23.560
How to actually have smart devices in your plant.

02:23.680 --> 02:29.040
Before then, you had primitive PLC systems that were all independent of one another.

02:29.040 --> 02:35.400
There was a couple vendors playing around with some serial forms of communication, but it was slow and clunky.

02:35.400 --> 02:51.380
And when DeviceNet came out, it opened you up to having very flexible installations of smart sensors and other types of devices than a PLC able to exchange data in your plant.

02:52.060 --> 02:57.460
In 1997, they released ControlNet, coaxial based.

02:57.460 --> 03:02.780
It's based on the 802.3b specification for its Layer 1.

03:02.780 --> 03:05.700
So that's your old school coaxial Ethernet.

03:05.700 --> 03:09.620
It uses the same type of Manchester signaling on the coax.

03:10.160 --> 03:12.920
Later in 2000, EtherNet IP came out.

03:12.920 --> 03:17.620
That's EtherNet Industrial Protocol, not to be confused with TCP IP.

03:18.120 --> 03:23.400
And it utilizes both UDP and TCP for transport, multicast, unicast.

03:23.400 --> 03:27.140
It's quite the interesting system.

03:27.380 --> 03:30.100
Again, nobody cares about CompoNet.

03:30.100 --> 03:33.760
So how does EtherNet IP actually work?

03:33.760 --> 03:35.940
Let's talk about the SIP stack.

03:36.560 --> 03:40.860
You have your TCP and your UDP.

03:41.660 --> 03:44.380
You have an encapsulation protocol.

03:44.380 --> 03:48.480
That's actually what is EtherNet IP, is that encapsulation protocol.

03:48.920 --> 03:53.100
You have different types of messaging, implicit and explicit.

03:53.100 --> 03:56.560
Implicit is just a device streaming information.

03:56.620 --> 03:59.640
Explicit is a request and a response.

03:59.640 --> 04:01.160
Single transactions.

04:01.740 --> 04:05.100
You have CIP network and transport.

04:05.100 --> 04:11.880
CIP is super unique in the sense that it was pre-EtherNet networks in the plant.

04:11.880 --> 04:17.240
So they invented their own method for doing things like routing, doing things like CRC checks.

04:17.240 --> 04:25.260
Everything that you take for granted that's handled for you at your EtherNet level, CIP has those mechanisms built into it as well.

04:25.260 --> 04:37.040
So when running on EtherNet-based networks, yes, you're taking advantage of TCP routing, but you're also taking advantage of CIP's network capabilities such as CIP routing.

04:37.580 --> 04:41.980
And then finally you have your application objects, your device profiles.

04:41.980 --> 04:52.720
These are actual C++ objects executing in the firmware of these devices that CIP hooks into, and that actually gives you the functionality for the protocol.

04:52.720 --> 04:54.240
And we'll talk about that.

04:55.460 --> 04:58.100
Like I said, objects.

04:58.100 --> 05:00.100
So what are CIP objects?

05:00.100 --> 05:08.300
CIP objects are fascinating because CIP operates a lot like a remote procedure call type protocol.

05:08.300 --> 05:20.960
You have objects in memory, in your firmware, and you have a class ID, and that ID number is a unique ID that references that C++ class.

05:20.960 --> 05:26.160
You have instance IDs, and they represent the instances of those classes.

05:26.360 --> 05:27.660
You have attributes.

05:27.660 --> 05:31.200
Your attributes are variables within those objects.

05:31.600 --> 05:39.120
And finally you have your services, which are actual functions in that object that you can call over the network.

05:39.800 --> 05:49.780
All of these different things, your class, your instance, your attribute, your service, they're addressed by unique identifiers, integer-based identifiers.

05:49.780 --> 05:51.300
So they're not using strings.

05:51.300 --> 05:52.780
They're not using names.

05:53.720 --> 06:13.140
When you send a CIP request, if I'm telling a device, hey, I want you to go turn this pump on, or I want you to energize 24 volts out to some device in the field, you do that with a CIP command that consists of what service you want to run, what class you're running it on,

06:13.140 --> 06:21.100
what instance you're executing that service actually against, and then sometimes what attribute that service is going to operate on.

06:21.100 --> 06:24.880
Maybe you're setting the value of a variable within that object.

06:26.780 --> 06:34.640
So let's talk about probably the most common, the most basic CIP object, the identity class.

06:34.640 --> 06:40.500
The identity class is instance ID 1, easy to remember.

06:40.880 --> 06:45.480
It has a default instance of that class, ID 1.

06:45.600 --> 06:53.100
And it supports a function, a service code of get all attributes, which is service 1.

06:53.300 --> 06:57.560
So, easy message to remember, 1, 1, 1.

06:57.560 --> 07:01.880
And that's going to tell you all the basic information about that device.

07:01.880 --> 07:05.300
So, we call that the who message.

07:05.960 --> 07:10.100
And in the who message, you're going to get things like the vendor of the device.

07:10.300 --> 07:21.320
And you can see, or maybe not because it's kind of cut off here at the bottom, but on the bottom you can see this JSON payload here where I've sent a who message to a device using a Python tool.

07:21.680 --> 07:27.180
And it's returned to me the vendor, the product type, the firmware revision.

07:27.180 --> 07:29.200
It's returned to me the device status.

07:29.200 --> 07:29.940
Is it running?

07:29.940 --> 07:30.740
Is it faulted?

07:30.740 --> 07:33.100
Is it in some kind of configuration mode?

07:33.600 --> 07:36.840
It's told me the serial number of the device.

07:37.400 --> 07:42.580
It's told me the actual product name, the string of the device, which is on the end over here so you can't see it.

07:44.820 --> 07:50.940
The who message retrieves all the information about the device from the identity object.

07:50.940 --> 07:57.060
And just like the identity object exists, there's hundreds of CIP objects within these devices.

07:57.060 --> 07:59.580
And all of them have a very specific purpose.

07:59.720 --> 08:05.860
They have very specific services which retrieve data out of them, or they perform functions within that object.

08:06.280 --> 08:12.260
And all of these objects all together make up your CIP protocol.

08:12.420 --> 08:14.940
So, different devices will have different objects.

08:14.940 --> 08:19.960
The core specification says which ones you're required to have, which ones are optional.

08:19.960 --> 08:24.740
And most vendors throw all that out the window and just say we're going to implement whatever we want.

08:24.980 --> 08:30.020
And so you're really up to the vendor to tell you what objects exist and why they exist and how to use them.

08:30.020 --> 08:32.160
And generally they don't like giving up that information.

08:34.580 --> 08:41.960
So, if we want to actually talk to one of these devices, access these CIP objects, there's three ways to do this.

08:41.960 --> 08:46.720
There's three forms of what we call explicit communication.

08:46.720 --> 08:51.180
That's where we're doing a request and we get a response from the device.

08:51.540 --> 08:53.220
There is UCMM.

08:53.280 --> 08:56.400
That's your Unconnected Message Manager.

08:56.820 --> 09:06.760
And what that means, we talked about how CIP has its own mechanisms for things like routing and other network services that TCP already provides.

09:07.060 --> 09:12.520
So, UCMM, that's kind of similar to saying, hey, I don't need a session.

09:12.520 --> 09:17.120
That's saying, you know, kind of like you're sending out a UDP request and getting it back.

09:17.120 --> 09:19.240
That would be the equivalent in networking terms.

09:19.240 --> 09:25.100
Now, this is over TCP, but I'm creating a CIP request without a CIP session.

09:25.100 --> 09:27.120
And I'm saying, hey, do this thing.

09:27.120 --> 09:28.160
Send me the data back.

09:28.160 --> 09:30.060
There's no CIP routing involved.

09:30.060 --> 09:32.740
There's no other CIP networking mechanisms involved.

09:32.740 --> 09:35.140
It's the most simple type of request.

09:35.660 --> 09:40.360
Then there's unconnected messaging, unconnected requests.

09:40.360 --> 09:43.920
Unconnected means I'm creating a CIP session.

09:43.920 --> 09:45.360
I'm creating a request.

09:45.360 --> 09:52.620
I'm using all of the capabilities of CIP routing, but I'm only going to do it for a single request.

09:52.780 --> 09:56.000
And so both sides know, hey, we spent all this effort.

09:56.000 --> 09:58.440
We set up a CIP route.

09:58.440 --> 10:00.460
We had multiple devices involved.

10:00.460 --> 10:02.300
I'm processing the request.

10:02.300 --> 10:06.400
I send you the response, and then we automatically destroy that connection.

10:06.760 --> 10:10.060
So it is a single session used for a single request.

10:10.660 --> 10:16.900
And finally, there are connected sessions, connected CIP requests.

10:16.900 --> 10:20.460
And that's identical to unconnected, but it leaves the connection open.

10:20.460 --> 10:29.980
So you can now reuse all of that information that you've specified for your routed path, for any other network infrastructure you set up between those devices.

10:29.980 --> 10:31.760
They'll persist that connection.

10:31.760 --> 10:35.760
You have a session number, and you can reuse that session number.

10:35.760 --> 10:41.220
That session number is interesting because that is completely independent of your TCP session.

10:41.300 --> 10:46.320
Your TCP session can make or break a hundred times, and CIP doesn't care.

10:46.320 --> 10:48.820
Your CIP session will persist.

10:49.300 --> 11:03.440
So you can see that layer of abstraction where we have duplications of infrastructure scaffolding in our networking environment where CIP has its own versions of things like sessions and routing, independent of TCPs.

11:04.940 --> 11:10.740
So let's talk about routing, because routing in CIP is one of the things that makes it super fascinating.

11:11.820 --> 11:21.640
CIP, because it is different types of networks, not just Ethernet, it has mechanisms in it to allow it to be backwards compatible with its predecessor networks.

11:22.020 --> 11:25.700
So here on the top, I have a CIP path.

11:26.360 --> 11:28.320
You can see IP addresses in there.

11:28.320 --> 11:31.420
That doesn't really look like a normal web path, does it?

11:31.960 --> 11:35.740
On the top, we have an Ethernet IP network.

11:35.740 --> 11:37.320
That's our SCADA network.

11:37.320 --> 11:41.180
This would be your process control network, perhaps, in your plant.

11:41.220 --> 11:42.980
And we're saying we're some device.

11:42.980 --> 11:46.020
We're starting here, somewhere on our plant floor.

11:46.220 --> 11:56.560
And I want to connect all the way down here to a card in this PLC, a module that is in the chassis of a PLC somewhere completely else in my plant.

11:57.220 --> 12:01.360
Well, we can build out a path to do that, because all these devices talk CIP.

12:01.420 --> 12:06.060
And we can say, hey, I want to talk to whatever device is 10.0.10.10.

12:06.420 --> 12:09.060
And that takes me to that Ethernet card in that chassis.

12:09.360 --> 12:15.900
I can say comma 1 to go out port 1 of that device, which actually takes me to the backplane of that chassis itself.

12:16.160 --> 12:18.460
I can say then, go to slot 10.

12:18.500 --> 12:21.160
And that takes me to slot 10 in my chassis.

12:21.760 --> 12:23.780
From there, I say, go out port 2.

12:23.780 --> 12:25.860
That's that purple 2.

12:25.980 --> 12:30.360
And that takes me out the control net port of that card.

12:30.360 --> 12:35.420
We've now transitioned from an Ethernet-based network onto a control net-based network.

12:35.600 --> 12:40.140
From there, I'm going to say, go to node 4, which is my HMI down here.

12:40.580 --> 12:47.880
From node 4, I'm going to say, go out port 3, which is the redundant Ethernet connection on that HMI.

12:48.300 --> 12:51.780
And then I'm going to say, go to 192.168.1.1.

12:52.080 --> 12:54.480
That's my PLC down here at the bottom.

12:54.480 --> 12:56.240
That's its Ethernet card.

12:56.240 --> 13:02.340
And finally, comma 1 to go to its backplane, comma 5 to go to slot 5.

13:02.380 --> 13:14.400
I just sent a request from one Ethernet network that had no Ethernet-based connections to another Ethernet-based network by utilizing CIP routing.

13:14.400 --> 13:16.500
I traversed a control net network.

13:16.500 --> 13:20.700
I traversed three different devices to get there.

13:21.900 --> 13:30.060
Essentially, we took two networks that, from a network topology standpoint, looked like they were air-gapped.

13:30.160 --> 13:33.640
And we got a command between them.

13:34.400 --> 13:43.720
That's what makes CIP routing so fascinating, is the security implications of what you can do on these devices between networks.

13:44.240 --> 13:45.720
It's freely available.

13:45.720 --> 13:49.640
You can route between these types of networks all day long, and these devices do not care.

13:51.800 --> 13:53.980
So now we're going to talk about the fun stuff.

13:54.820 --> 13:58.720
Just a quick disclaimer, this is critical infrastructure.

13:58.920 --> 14:03.360
We are going to be talking a little bit about how to get started hacking critical infrastructure.

14:03.620 --> 14:07.420
So with that, we'll put on our blue team hats, not our red team hats, right?

14:08.420 --> 14:12.100
These systems do protect humans, right?

14:12.100 --> 14:15.300
When hacking into these systems, you never want to hack a live system.

14:15.300 --> 14:17.480
You could kill people, many people.

14:17.480 --> 14:19.880
These systems protect the environments.

14:19.880 --> 14:26.180
When hacking into these systems, there are catastrophic environmental consequences if you do something incorrectly.

14:26.500 --> 14:28.820
And finally, physical infrastructure itself.

14:28.820 --> 14:32.200
You could take down entire refineries, power grids.

14:32.340 --> 14:37.160
The astronomical impacts of these systems when they go down is quite large.

14:37.540 --> 14:41.880
We don't do this for the sake of breaking into things because it's fun.

14:41.880 --> 14:47.400
We do this for the sake of knowing how to protect our critical infrastructure, right?

14:49.260 --> 14:50.180
Okay.

14:50.180 --> 14:51.520
There's the scary talk.

14:51.520 --> 14:52.800
Let's do the fun talk.

14:52.800 --> 14:53.880
Fuzzing!

14:53.880 --> 14:55.460
Everybody like fuzzy things?

14:55.460 --> 14:56.680
I like fuzzy things.

14:56.680 --> 14:58.080
My dog is fuzzy.

15:00.040 --> 15:06.780
Fuzzing is when we send targeted random values to a device through the protocol.

15:07.200 --> 15:13.000
So we talked about how we have these ID numbers for classes, instances, attributes and services.

15:13.220 --> 15:14.500
They're just numbers.

15:14.500 --> 15:23.960
What if we selected some number ranges and just sent requests where we said, hey, I want to send a specific service.

15:24.020 --> 15:31.160
Maybe I'm going to use the GetAttributeListService, service three, on every instance zero.

15:31.280 --> 15:35.220
And instance zero is the singleton or static instance of a class.

15:35.460 --> 15:39.680
And I'm going to say, do it on every instance number between X and Y.

15:39.720 --> 15:41.540
I'm just going to see what I get back.

15:41.540 --> 15:51.720
And that's a really common way to find out what C++ objects in my firmware are attached to the CIP protocol within that device.

15:51.800 --> 15:57.980
That gives me very quick and dirty knowledge of what actually is in there in the device.

15:58.340 --> 16:02.240
How do I find what functions I have available to me?

16:02.240 --> 16:05.620
Because there's no way to say, hey, tell me what you can do.

16:05.760 --> 16:07.760
The vendors don't want it to have that function, right?

16:07.760 --> 16:10.580
So it's not going to give you a list of everything it supports.

16:10.580 --> 16:12.300
You have to go find it.

16:12.640 --> 16:15.640
So fuzzing is a really cool technique to do this.

16:16.280 --> 16:17.980
So here's a fuzzing example.

16:18.440 --> 16:21.540
I've built a simple Python script here.

16:21.600 --> 16:24.900
I'm using service, zero, three.

16:25.100 --> 16:27.260
That's GetAttributeList.

16:27.820 --> 16:33.020
I'm using class code of class ID, as you can see, which is in my for loop.

16:33.020 --> 16:35.960
And I'm saying, I just want to hit every class from one to a thousand.

16:35.960 --> 16:38.140
Let's just see what we can find, right?

16:39.240 --> 16:40.740
I'm using instance zero.

16:40.740 --> 16:43.820
I'm querying the singleton instance of these classes.

16:44.280 --> 16:49.240
And I'm using attribute zero, which is the null attribute, meaning I don't need an attribute in this case.

16:50.540 --> 16:55.540
At the bottom, you're going to see an output, a snippet of what this script returned here.

16:55.540 --> 17:01.320
And you can see, we have a whole bunch of these destination unknown, class unsupported, instance, yada, yada, yada.

17:01.440 --> 17:04.160
Basically telling me, hey, there's nothing there.

17:04.160 --> 17:04.900
Good luck.

17:04.900 --> 17:05.760
Try again.

17:05.760 --> 17:07.800
But you can see we've got two hits there.

17:07.800 --> 17:10.560
And I've put those in red boxes.

17:10.680 --> 17:17.240
The first one, class 0xA1, we've got a service not supported.

17:18.040 --> 17:20.320
Okay, what does that tell us?

17:20.320 --> 17:21.860
There's an object there.

17:22.040 --> 17:27.480
It doesn't support the GetAttributeList service, but we know there's an object there now, right?

17:27.480 --> 17:35.280
So if we wanted to expand on our fuzzing, what we'd do is reset up our script to go hit every service code and see what service codes give us errors.

17:36.260 --> 17:37.740
That's good to know, right?

17:37.740 --> 17:44.700
We can now start pentesting that particular object and figuring out what it's capable of, what data it's storing.

17:45.160 --> 17:47.680
We've got another hit, class 0xAA.

17:47.700 --> 17:53.140
In this case, this is a known object that's actually part of the protocol specification.

17:53.640 --> 17:56.340
It's the Ethernet TCP IP object.

17:56.340 --> 18:02.010
It's the object that stores the device's IP address, MAC address, diagnostics counters for its Ethernet ports.

18:02.700 --> 18:05.740
And we've got a service not supported from it as well.

18:06.260 --> 18:07.560
Well, that's easy.

18:07.560 --> 18:13.240
I'm just going to go get the spec out and say, hey, what services does this object actually have in it as part of the specification?

18:13.560 --> 18:16.320
Because I know this device now has that object.

18:16.660 --> 18:19.760
Now, granted, I'm talking to it on an Ethernet-based network.

18:19.760 --> 18:21.320
It better have that object.

18:21.320 --> 18:31.460
But the fact that it's exposing that object to me on the network means I can now access that object, I can query that object, and I can control that object.

18:31.460 --> 18:46.320
Because as part of the CIP specification, the TCP object allows me to remotely set the IP address of the device, change its gateway, change its subnet mask, without requiring any authentication mechanism.

18:47.200 --> 18:54.060
You can modify the script right here to go change the IP address of this device just like that, and the device would have a new IP address.

18:56.660 --> 19:00.800
So, that's kind of a quick and dirty intro into fuzzing.

19:01.140 --> 19:02.520
What do you do next?

19:03.020 --> 19:08.540
Well , in the Rockwell-Allen-Bradley world, we have what we call a Minerf.

19:08.540 --> 19:10.300
Really fun word to say.

19:10.540 --> 19:14.060
That is a major non-recoverable fault.

19:14.060 --> 19:17.320
And it is the easiest thing to do to a controller.

19:17.320 --> 19:20.620
It's also perhaps one of the most dangerous things to do to a controller.

19:20.740 --> 19:25.540
A Minerf will stop whatever device is from executing.

19:25.540 --> 19:27.400
So, it will halt execution.

19:27.460 --> 19:32.620
It will cause it to dump its entire configuration out of memory.

19:33.020 --> 19:35.560
It has no more program, no more configuration.

19:35.820 --> 19:41.660
It is just a dumb, dead box waiting for a technician or engineer to plug into it and give it a new program.

19:42.720 --> 19:46.920
That's dangerous because, as we talked about, these devices are running critical infrastructure.

19:47.180 --> 19:56.960
So, you can imagine, you have some computer in your plant, and it's controlling the pressure on a pressure vessel that's at 10,000 PSI.

19:56.960 --> 19:59.060
And all of a sudden, that computer just halts.

19:59.060 --> 20:00.800
It says, no, I'm done.

20:00.800 --> 20:07.920
And, you know, you might have some valve feeding that system, providing whatever product is going into that vessel.

20:07.920 --> 20:12.780
And if it can no longer say, hey, we're getting too much pressure, we need to close that valve.

20:12.780 --> 20:15.580
And that vessel is just going to overpressure and blow up.

20:15.920 --> 20:26.680
Now, presumably, your mechanical engineering team has put some other types of safety mechanisms in place, like pressure relief valves or any other type of mechanism like that.

20:26.680 --> 20:28.600
Like, generally, these systems are fail-safe.

20:28.600 --> 20:32.700
So, if one of these computers crashes, you have relay logic.

20:32.700 --> 20:38.860
And as part of the electrical installation, how these systems are wired, your valves should go to whatever their safe position is.

20:38.860 --> 20:40.180
Maybe you're venting that vessel.

20:40.180 --> 20:43.500
Maybe you're cutting off the flow of product into that vessel.

20:43.500 --> 20:49.160
But still, you have caused a disruption that very potentially could have major impacts.

20:49.800 --> 20:57.420
The reason minerfs are easy to find from a fuzzing perspective is these systems do integrity checks on themselves continuously.

20:58.600 --> 21:09.280
And if they see that there was a failure to validate input and it caused a buffer overflow, the system's going to go, hey, I don't have data integrity anymore.

21:09.440 --> 21:10.900
I need to minerf.

21:11.880 --> 21:13.560
And boom, it's gone.

21:13.600 --> 21:23.580
So, you could presumably go through and, during your fuzzing, have given it a service ID that they didn't account for when they do their input validation.

21:23.580 --> 21:28.480
And all of a sudden, the code goes off into some random branch that it's not supposed to go out into.

21:28.800 --> 21:31.140
And it fails that integrity check in minerfs.

21:31.920 --> 21:37.840
In my experience, when I'm doing fuzzing, I can find, on average, three minerfs a day.

21:39.840 --> 21:43.480
So, that just tells you how often these minerfs occur in these devices.

21:45.860 --> 21:50.560
I would say that I spent many, many hours in Wireshark.

21:50.560 --> 21:52.600
I'm sure everybody here knows what Wireshark is.

21:52.600 --> 21:57.980
Wireshark has awesome, awesome capabilities at decoding CIP.

21:58.320 --> 22:05.380
I don't know who, but some poor soul spent a lot of time building the CIP plugin for Wireshark, and it's absolutely fantastic.

22:05.380 --> 22:08.020
So, definitely utilize Wireshark.

22:09.980 --> 22:11.340
And that's it.

22:11.340 --> 22:12.600
So, thank you.

22:12.600 --> 22:13.720
Thanks for coming.

22:13.720 --> 22:15.920
I'm going to leave you with a couple tools.

22:16.140 --> 22:25.880
So, first, if you go to the ICS Village GitHub account in our CTF repository, every script and demo I used to build this presentation is in that repository.

22:25.880 --> 22:27.900
You can actually get that tooling to do fuzzing.

22:27.900 --> 22:31.040
I have fuzzing tools in that repository to get you started.

22:31.840 --> 22:34.260
You can also use the Molex Ethernet IP tool.

22:34.260 --> 22:36.340
This is a free tool provided by Molex.

22:36.580 --> 22:38.940
It's for doing device validation and testing.

22:39.120 --> 22:41.100
Awesome tool for this kind of stuff.

22:41.500 --> 22:46.940
And finally, if you're a Python guy and you just want to do it all on your own, PyCom 3 is a fantastic library.

22:47.280 --> 22:49.600
I am not the developer, but I know the developer.

22:49.600 --> 22:52.500
He is awesome, very open to suggestions.

22:53.440 --> 22:54.980
And I say, just go to eBay.

22:55.020 --> 22:56.020
Find some hardware.

22:56.020 --> 22:57.060
That's what I do.

22:57.140 --> 22:59.920
This stuff on eBay isn't cheap, but it's not too expensive.

22:59.920 --> 23:03.020
It won't break the bank if you want to have your own little cyber range at home.

23:03.720 --> 23:07.200
And finally, once you find something, report it to sysevents.

23:07.640 --> 23:14.180
They'll help you get connected with the vendor, build those relationships for you, and that way the vendor can get it fixed.

23:15.200 --> 23:16.420
And that's it.

23:21.820 --> 23:22.820
Thank you.
