WEBVTT

00:00.000 --> 00:00.800
Hello, everybody.

00:00.800 --> 00:01.740
Thank you for coming.

00:02.140 --> 00:07.260
This is There and Back Again, which is all about discovering OT devices across protocol gateways.

00:07.620 --> 00:08.900
My name is Rob King.

00:09.040 --> 00:11.100
There's my face if you want to see it twice.

00:11.300 --> 00:12.280
It's right there.

00:13.220 --> 00:16.460
So let's talk about how did we get here?

00:17.840 --> 00:35.480
So when we talk about OT, we talk about ICS, we talk about SCADA, we often think about these super cool looks like from the 1990s or maybe 80s with a good budget sci-fi thing with a control room and uniforms and bleepy things and all that.

00:35.480 --> 00:37.500
And that is part of it and it's super great.

00:37.640 --> 00:44.440
This is a control room from I think it's a refinery in Germany, but it's from Wikimedia, so very nice of them.

00:44.860 --> 00:55.000
But what we're really talking about as well and what we tend to kind of abstract away from as security practitioners is the fact that we're still talking about these machines that actually do things in the real world.

00:55.000 --> 01:01.360
They spin, they pump, they flap, they poke, whatever it is they do.

01:02.240 --> 01:06.300
And so we need to talk about how we actually control those devices.

01:06.600 --> 01:10.760
And by the way, we've got 43 slides to get through in 25 minutes, so I believe in you.

01:10.860 --> 01:12.900
So we're going to go fast.

01:13.200 --> 01:15.100
So industrial control technology.

01:15.560 --> 01:29.140
So it started with, you know, somebody having to stand there and push a button and pull a lever and read things off, you know, read symbols off things and then type or whatever, which is a horrible job that no one should ever have to do.

01:29.520 --> 01:32.380
And so we thought maybe we should automate this a bit more.

01:32.660 --> 01:36.440
So we came up with this concept of simple electronic logic.

01:36.440 --> 01:39.060
So we say, okay, that's a major improvement.

01:39.060 --> 01:47.940
We can have things that aren't just simply repeated over and over, but you can have a little bit of, you know, if then or do this three times and then do something else and it's all great.

01:48.140 --> 01:54.360
But those devices, those controllers were connected to the machines that were being controlled.

01:54.360 --> 02:01.900
If you needed to change something or check on something, you had to physically walk over there and, you know, like a pilgrim and touch things, right?

02:01.900 --> 02:03.380
Push buttons, do all that.

02:03.620 --> 02:07.000
Still a major improvement, but not particularly efficient.

02:07.800 --> 02:14.280
And then so someone had this great idea of what if we make the wires that connect those controllers longer?

02:14.520 --> 02:19.840
And we put all of the controls and the dials and everything all in one spot.

02:19.860 --> 02:22.620
This was the concept of distributed control systems.

02:23.020 --> 02:27.820
And so you put everything in one room and so you can check on the state of your factory in a glance, right?

02:27.960 --> 02:29.500
And this was great.

02:29.500 --> 02:30.360
This was much more efficient.

02:30.360 --> 02:36.280
You still had to occasionally go out and check on things, but it made it easier to get an overview of the whole process.

02:37.140 --> 02:47.200
But it was still a problem in that each one of those, you know, dials or switches or gauges or whatever was linked more or less to one specific device, right?

02:47.200 --> 02:49.680
So you still had a lot of wiring and a lot of cabling.

02:50.500 --> 02:53.280
Cats and dogs living together in a mass hysteria, you know, all that.

02:54.700 --> 03:07.320
If you ever watched, if you're of a certain age, if you ever watched The China Syndrome, Jane Fonda, Jack Lemmon, both of them nominated for Oscars, great movie, a little alarmist, there was a problem where one of these mechanical gauges got stuck and we almost had a nuclear meltdown.

03:07.740 --> 03:10.620
The movie was released just before Three Mile Island, it was very prophetic.

03:10.620 --> 03:16.800
Anyway, so we're like, hey, what if we started putting things like these newfangled computers in there?

03:16.800 --> 03:20.040
Well, now I see your problem, there's a computer in there.

03:20.040 --> 03:30.180
But what happened was we started coming up with the idea of using this newfangled computer intelligence technology to make buses.

03:30.180 --> 03:43.500
So instead of having tons of wires running everywhere, there was enough intelligence in the end devices and the controller devices to send signals, multiplex signals over a single set of cabling, a single set of wires, right?

03:43.660 --> 03:53.260
This is actually, this is an example of the Hewlett Packard instrument bus, which this was back when Hewlett Packard made laboratory equipment and not printers that made you sad.

03:53.660 --> 04:04.320
And also fun note, this was adapted to be the bus for like the Commodore 64, Commodore PET, was also HPIV, just kind of adapted and slower.

04:04.320 --> 04:08.540
So you were doing lab science work every time you used your Commodore 64.

04:08.880 --> 04:19.540
But what was neat about this is there was enough intelligence that you could say, okay, I'm going to send a message and I want it to go to device number 8 or 7 or whatever.

04:19.540 --> 04:22.540
And the other devices knew not to respond to that message, right?

04:22.540 --> 04:25.100
And you only had to have one bit of wiring.

04:25.780 --> 04:37.260
Now, HPIV was, it was designed more for like bench scenarios, like laboratory equipment, oscilloscopes, cool stuff, science, but not large industrial things.

04:37.520 --> 04:40.100
There was a fairly short maximum cable length, that sort of thing.

04:40.100 --> 04:42.720
Wasn't designed for particularly noisy environments, all that.

04:42.840 --> 04:49.320
So Modicon came up with the idea of Modbus, which you've all heard of, and if you haven't, you're about to.

04:49.820 --> 04:56.980
And so that was actually the first Modicon PLC, which Modicon got bought out by, was it Schneider Electric?

04:56.980 --> 04:57.820
Somebody tell me.

04:57.820 --> 04:59.080
Schneider Electric, I think.

04:59.580 --> 05:01.200
Either that or Siemens, Schneider.

05:01.240 --> 05:07.860
Anyway, and the standard protocol for Modicon, Modbus, became controlled by an industry consortium.

05:07.860 --> 05:16.240
So it's kind of an open standard now, very simple, but allowed this concept of a bus architecture in an industrial environment.

05:16.240 --> 05:21.260
So you could say, okay, and this is a little bit more modern, this is talking about Modbus TCP, but the principle is the same.

05:21.260 --> 05:29.140
You can talk to lots of different devices by their address using a common protocol and more or less a common set of physical media.

05:29.560 --> 05:32.140
Made things a lot more efficient, a lot easier.

05:32.480 --> 05:38.620
But then, as time marches on, we started converging on IP and Ethernet.

05:38.620 --> 05:58.440
All of these protocols either predate IP and Ethernet becoming standard or predate them entirely, you know, take your pick, or predate them even becoming useful in the kinds of environments that industrial situations involve, like noisy electrical environments and vibration and things like that.

05:58.760 --> 06:03.400
So we started doing industrial Ethernet because it's a commodity, right?

06:03.400 --> 06:09.460
Ethernet, IP, commodity software, commodity technology, it's cheaper, it's easier to use, it's easier to integrate.

06:09.740 --> 06:16.180
This is fantastic, but it does lead to now you can have your industrial systems connected directly to the Internet, which is a bad thing.

06:16.180 --> 06:19.000
You really shouldn't do that, but this was just an example.

06:19.000 --> 06:20.480
I'm not going to harp on this too much.

06:20.480 --> 06:29.540
Other people have talked about IP convergence and security and OT, but just for the record, I really should not see these sorts of things when I do a public scan of the public Internet, but I do.

06:29.540 --> 06:31.280
So you should fix that.

06:32.480 --> 06:37.240
But the advantages of this convergence are undeniable, right?

06:37.240 --> 06:41.340
It makes it much easier to work with, makes it much easier to integrate into existing systems.

06:42.160 --> 06:47.280
But now that they're all connected, I want to discover these devices.

06:47.280 --> 06:49.380
I want to find them on the network.

06:49.500 --> 06:55.520
I've spent most of my career searching for devices, trying to find them, trying to fingerprint them.

06:55.520 --> 06:56.200
I love it.

06:56.200 --> 06:57.860
It's super fun.

06:57.940 --> 06:59.280
I'm a lot of fun at parties.

06:59.520 --> 07:05.840
So this is Modbus when they took Modbus and adapted it to TCP.

07:06.180 --> 07:19.380
So what they did quite literally was just put a framing header on the front so you knew how long the message was going to be and then they took the core of the Modbus protocol and shoved it on top of TCP and it works.

07:19.380 --> 07:20.320
It works fine.

07:21.180 --> 07:26.320
But it's not ‑‑ it was never designed to really be supporting discovery.

07:26.400 --> 07:30.740
They kind of assumed that if you've got your factory, you should know what's in your factory, right?

07:30.740 --> 07:38.160
Well, factories have gotten bigger, technology has gotten bigger, shadow IT, we now have shadow OT, so it's good to know what's actually going on.

07:38.620 --> 07:43.740
And then this is just to give you an example, this is literally explaining how they're shoving it into the TCP data segment.

07:43.740 --> 07:46.720
It's just the entire Modbus message plus some framing.

07:46.720 --> 07:48.840
It's treated as a normal TCP stream.

07:49.080 --> 07:50.160
There's no magic.

07:51.480 --> 07:55.920
But Modbus as a protocol is very simple, which is not surprising.

07:55.920 --> 08:02.960
It was created in, I think, 1978, so it's about as old as I am and I'm, you know, not very smart.

08:03.200 --> 08:06.320
So it can do things like read a register.

08:06.320 --> 08:10.540
Please give me the number that's in register, you know, 2 or whatever.

08:10.920 --> 08:11.900
And you get that back.

08:11.900 --> 08:12.860
But that's all you get.

08:12.860 --> 08:18.360
There's not a lot of meta information, there's not a lot of self‑describing data, and that was on purpose, right?

08:18.360 --> 08:21.180
They don't want to waste the bandwidth.

08:21.180 --> 08:23.980
They don't want to waste the bits on the wire.

08:24.520 --> 08:27.360
It was much more important to have that maybe be error correction or something like that.

08:27.360 --> 08:30.600
So how do we identify a Modbus device?

08:30.600 --> 08:37.280
Well, this is the list, I know you're all like, wait, wait, there's one more, and I was like, yes, there is, but next slide.

08:37.280 --> 08:43.080
This is a list of all the possible ‑‑ all the standard function codes in Modbus.

08:43.180 --> 08:45.820
And you're like, okay, well, you know, maybe one of these can work.

08:45.820 --> 08:48.760
Like there's that report server ID down there, that seems useful.

08:48.840 --> 08:50.540
That only works on Modbus serial.

08:50.740 --> 08:52.860
Or occasionally on TCP, but it doesn't tell you much.

08:52.860 --> 08:55.680
It's just, yeah, my unit ID is 3.

08:55.680 --> 08:56.820
Which is, you know, great.

08:56.820 --> 08:58.140
I now know that your unit ID is 3.

08:58.140 --> 08:59.300
I still don't know what you are.

09:00.320 --> 09:12.720
Well, Modbus 1.1 in 2004, 6, something like that, gave us the idea of the encapsulated interface transport.

09:12.720 --> 09:28.080
So just like how they took Modbus and they shoved the entire thing inside TCP with some framing, they then shoved this entire sort of additional protocol that's much more complex entirely in the Modbus frame, the Modbus payload.

09:28.080 --> 09:31.240
Using opcode 2B, or not 2B.

09:31.840 --> 09:38.100
And one of the extended operations that they can do is read device identification.

09:38.540 --> 09:49.780
And read device identification, you can say, hey, you can see here that the function code is encapsulated interface transport, and then suddenly there's this new additional secondary opcode, MEI type, read device identification.

09:50.600 --> 09:53.520
And what that gets us back is much more information.

09:53.520 --> 09:57.440
Vendor name, product code, all sorts of useful things.

09:57.440 --> 10:04.600
And in fact, this is if your device supports MEI, it's required to at least support vendor name, product code, major or minor revision.

10:04.920 --> 10:09.260
Most devices also support vendor URL, product name, model name, all that good stuff.

10:09.360 --> 10:20.460
It's all exposed as objects because it was 2004 and everything had to be object oriented and there was probably, you know, somebody made a lot of money saying, oh, yes, object oriented Modbus, but it is, and it's kind of nice.

10:20.520 --> 10:28.440
So you can do that, and you can get all sorts of information automatically when you do this, which is very nice for discovering Modbus.

10:29.160 --> 10:37.380
But now let's talk about the second worst named, second most confusingly named protocol in this talk, which is distributed network protocol 3.

10:37.380 --> 10:40.620
Does anybody, just show of hands real quick, does anybody use DMP3?

10:40.620 --> 10:42.920
It's not super, okay, yeah, all right.

10:42.960 --> 10:54.100
So distributed network protocol 3 is a standard industrial protocol, but it's only, I don't want to say only, it's primarily used in utility distribution.

10:54.100 --> 10:56.780
So electricity, water, things like that.

10:56.780 --> 10:59.680
Super useful, I like having power, I like having water.

11:01.040 --> 11:07.000
DMP3 was designed later than Modbus, and so it has a much richer set of semantics.

11:07.000 --> 11:17.480
This beautiful diagram explains the level of, depending on how you want to look at it, complexity or sophistication of DMP3.

11:17.760 --> 11:26.240
DMP3 has its own framing, it has its own checksumming, it has its own transport layer, it has its own addressing scheme that's much more complicated than Modbus's addressing scheme.

11:26.240 --> 11:35.160
Modbus was just, hey, unit 23 on the shared bus, whatever, do this thing, maximum of 255 devices.

11:35.660 --> 11:37.860
This supports much, much more.

11:37.860 --> 11:47.960
But just like with Modbus where they took the Modbus protocol and just kind of plopped it on top of TCP, they really did that with DMP3.

11:47.960 --> 11:59.060
So DMP3, they didn't just take the user application layer or the transport layer or anything, they took the whole shebang, the whole kit and caboodle, and just plopped it on top of TCP.

11:59.440 --> 12:06.680
Which is great in that you can have a shared implementation and if you're wanting to talk across different physical media, it's all the same code and that's fantastic.

12:06.800 --> 12:11.160
But it also makes discovery of these devices a little problematic.

12:12.000 --> 12:22.920
So DMP3 devices, if they're on an IP network or they're speaking through an IP protocol gateway, they will have an IP address, as one does, but they will also have a DMP3 address.

12:23.160 --> 12:30.360
And also, also, on the gripping hand, they will only talk to their designated primary device.

12:30.360 --> 12:42.760
So when you configure a DMP, I mean, usually, it weighs around everything, but usually when you configure a DMP3 device, you say your primary is, you know, at DMP3 address 7 or whatever.

12:42.780 --> 12:44.860
And then it will only talk to that device.

12:44.860 --> 12:51.360
So if you connect to a DMP3 device via TCP, you will get basically nothing.

12:51.360 --> 12:54.880
You'll just get sort of an empty, you know, session, empty channel.

12:55.260 --> 13:09.920
And if you want to ask that device, you want to query that device for any information, you have to then construct an entire DMP3 transport layer message and application layer message and then send that across the wire with the appropriate destination address for the device you're talking to,

13:09.920 --> 13:12.800
but also you have to spoof the primary address.

13:12.840 --> 13:16.940
So that's a problem because there's, you know, 65,000ish, there's a couple of reserved ones.

13:16.940 --> 13:19.380
Addresses, it would take a long time to guess those.

13:19.860 --> 13:21.620
So what can we do about that?

13:22.020 --> 13:24.380
Well, I just said all that.

13:24.380 --> 13:27.920
Well, what we can do is there's banner sniffing for DMP3.

13:27.920 --> 13:34.180
Not a guarantee, and there's what's sad is the fallback is that you do have to enumerate the address space, but I'll cover that in a second.

13:34.440 --> 13:48.860
But most DMP3 devices, not all, not all, but most, when you connect to them via TCP, will send what's called an unsolicited response, which if you didn't solicit it, it's not a response, it's just a message, but I digress.

13:49.340 --> 13:57.220
But it will say, okay, you know, yeah, my clock is out of sync or here's the flags that have changed since the last time we talked or whatever, but the important thing is that's a full DMP3 message.

13:57.220 --> 14:04.880
It's got the entire transport layer in there as well, including the device's own address and the device that it's talking to, which is its primary.

14:04.960 --> 14:14.100
So you can say, oh, okay, well, great, now I know your address is whatever, because it's the source address, and I should pretend to be whatever the destination address was.

14:14.100 --> 14:15.240
Super useful.

14:15.320 --> 14:17.040
Doesn't always work.

14:17.120 --> 14:19.260
They don't always send these unsolicited responses.

14:19.260 --> 14:23.300
Sometimes they'll send them only if they haven't talked to the primary for five minutes.

14:23.300 --> 14:24.240
Sometimes they send them every time.

14:24.240 --> 14:25.520
Sometimes they never send them.

14:25.660 --> 14:30.780
But if you're doing DMP3 device discovery, sometimes you luck out and you just get one and it's great.

14:31.180 --> 14:40.720
But otherwise you have to go and enumerate the entire address space, which would take a really, really long time, because there's, you know, 65,000 possible combinations on the one end and the other end.

14:41.020 --> 14:49.800
The good news there is that most of those devices or most networks, they tend to put addresses at the lower end of the range.

14:49.800 --> 14:52.640
So really you're only talking about maybe the first 1,000 or so.

14:52.640 --> 14:54.200
You'll get at least a few hits.

14:54.480 --> 14:55.660
But it's not a guarantee.

14:56.140 --> 15:05.220
But anyway, once you've got that connection, once you've got that address guessed or determined or sniffed or spoofed or whatever, you can then get these DMP3 attributes.

15:05.220 --> 15:07.960
They're not quite standard, but they're pretty standard.

15:07.960 --> 15:13.420
And you can say, hey, give me your software version, your hardware version, your host name, all that good stuff.

15:13.500 --> 15:15.540
And there is, in fact, what you get.

15:15.860 --> 15:17.940
By the way, this was a lot of fun to set up.

15:17.940 --> 15:21.160
And when I say fun, I mean that I hated my life.

15:21.160 --> 15:22.280
But I got it working.

15:22.620 --> 15:25.420
So the lab was a mess, but I got it working.

15:26.020 --> 15:28.620
And you can discover DMP3.

15:29.180 --> 15:31.580
But now, let's move on.

15:31.780 --> 15:39.060
I said DMP3 was the second most confusingly named protocol we're going to talk about.

15:39.340 --> 15:44.880
The first most confusingly named, if you come from an IT background, is Ethernet IP.

15:45.320 --> 15:48.900
Because the IP does not stand for Internet protocol, it stands for industrial protocol.

15:48.900 --> 16:00.220
So when we talk about Ethernet IP, we are talking about Ethernet IP on top of IP on top of Ethernet and the two IPs means something different and one of the Ethernets doesn't actually mean Ethernet.

16:00.220 --> 16:01.680
So it's kind of a problem.

16:01.840 --> 16:04.300
But anyway, super fun.

16:04.300 --> 16:05.440
It's a very pretty protocol.

16:05.440 --> 16:06.200
I really like it.

16:06.200 --> 16:10.500
But I really like writing protocol parsers like I would do it if they didn't pay me.

16:10.500 --> 16:12.640
But they do pay me, which is great.

16:12.640 --> 16:13.880
So please keep paying me.

16:14.780 --> 16:15.440
Ethernet IP.

16:15.440 --> 16:21.480
So Ethernet IP is an adaptation of SIP, which is the common industrial protocol.

16:21.480 --> 16:32.520
Used to be an information protocol from Rockwell, but just like Modbus is now controlled by a consortium of whatever, SIP is now controlled by a consortium of whatever.

16:32.520 --> 16:36.360
I still don't know what ODVNA stands for.

16:36.360 --> 16:38.560
I cannot find it, but that's the name of the consortium.

16:38.560 --> 16:40.700
I'm assuming A is association, but I don't know.

16:40.700 --> 16:44.740
Anyway, SIP is an abstract protocol.

16:44.980 --> 16:47.640
Much like SNMP defines lots of encodings.

16:47.640 --> 16:51.500
You can use dir and bur and sir and all those.

16:52.260 --> 16:56.400
Which everyone out there who's ever worked with SNMP is like, no, no, please, stop talking about SNMP.

16:56.540 --> 16:57.500
ASN1, no.

16:57.500 --> 16:58.600
It's terrifying.

16:58.880 --> 17:01.920
But SIP has different adaptations to different protocols.

17:02.040 --> 17:07.060
So Ethernet IP is the SIP adaptation for IP networks, right?

17:07.060 --> 17:10.820
But there's also standard adaptations for combo net, control net, device net.

17:10.820 --> 17:14.520
There's one for CAN bus, you know, all this, right?

17:14.740 --> 17:20.880
But the point is, once you get there, you're talking this abstract protocol, which is defined as objects and messages, right?

17:20.880 --> 17:26.300
SIP defines the standard set of objects and messages and attributes on those objects.

17:27.700 --> 17:31.560
And so, but Ethernet IP is the lower level, right?

17:31.560 --> 17:33.280
You want to connect, or for an IP network.

17:33.280 --> 17:36.340
So you want to connect to a device that speaks SIP.

17:36.340 --> 17:40.680
You connect on an IP network via using Ethernet IP, and then you start talking SIP.

17:40.680 --> 17:44.360
But before you start talking SIP, you're talking Ethernet IP.

17:44.360 --> 17:52.160
And Ethernet IP provides a full device discovery mechanism right out of the box, super nice, it's great, called list identity.

17:52.360 --> 18:04.680
So list identity is, you can see it here, it's command list identity, and, oh, I want SIP identity, and then you get back, you know, Rockwell automation, Alan Bradley, program a logic controller, blah, blah, blah, blah, which is great.

18:04.680 --> 18:10.160
And you can send that via TCP, you can actually do that as a UDP broadcast, and devices will just respond and say, here I am.

18:10.320 --> 18:11.440
And that's great.

18:11.480 --> 18:12.480
Problem solved, right?

18:12.480 --> 18:13.740
We're Ethernet IP done?

18:13.740 --> 18:14.860
No, I say.

18:14.860 --> 18:16.920
Oh, and here's what it looks like when you connect.

18:17.080 --> 18:18.760
There's the devices you can pull.

18:18.920 --> 18:25.400
But I don't want just that device, because remember, we're talking about protocol adaptation.

18:25.400 --> 18:31.440
We're talking about multiple devices being adapted or having gateways to IP networks, right?

18:31.440 --> 18:47.360
What if we're talking about one of these racks where you've got an Ethernet IP adapter, and in that rack you've got a PLC and a motor controller and a thermal monitor and a spline reticulator and all that, and they're connected via some other back plane or some other transport protocol.

18:47.780 --> 18:57.760
Well, what I can do is I can connect via Ethernet IP to that Ethernet IP adapter, and one of the objects in SIP is a connection object.

18:58.080 --> 19:01.320
And another object in SIP is a connection manager object.

19:01.320 --> 19:04.260
And another object in SIP is an identity object.

19:04.460 --> 19:17.760
So if I just connect straight to the Ethernet IP adapter, and I say, hey, I want all of the attributes off of your identity object, I'll get back more or less what I got back from the list identity, just via Ethernet IP.

19:17.760 --> 19:23.820
But now I'm at SIP, it's a higher level of semantic meaning, whatever, but it's still more or less the same thing.

19:23.820 --> 19:38.720
But the magic that comes in is that you can then say, hey, connection object, please, or connection manager object, please get me a connection to the device at this other address, right?

19:38.720 --> 19:39.640
And what do you get?

19:39.640 --> 19:48.820
Well, now you can say, okay, it'll hand you back, it'll say, okay, great, here's a connection to this other device, or I can't make a connection , you know, whatever, there's an error.

19:49.200 --> 20:06.080
But you can now say, okay, I want you to forward this request to get all the identity attributes to this other object through that connection, and it will do so, and it will actually forward that theoretically recursively all the way down to this other object and then relay everything back up to you.

20:06.220 --> 20:09.500
And so now you can discover everything in the rack.

20:09.940 --> 20:17.180
It does use sort of, if you remember source routing, you actually do have to construct a path to get there.

20:17.600 --> 20:19.760
So how am I doing on time?

20:19.760 --> 20:20.020
Okay.

20:20.020 --> 20:33.020
So you can say, okay, I want to get all attributes from the identity object, you can see here, get attributes all, instance one, there's only ever one instance of an identity object.

20:33.200 --> 20:34.500
Port segment.

20:35.400 --> 20:43.040
So I'm trying to get slot 12 of this Rockwell RS links device on its back plane, please give me that.

20:43.420 --> 20:46.820
And what you get is voila, you get this.

20:46.820 --> 20:53.440
So what we have here is, here's the Ethernet IP adapter, and the PLC, and there's all these other devices.

20:53.440 --> 20:58.640
I want to discover all these other devices, because I'm not satisfied with just talking to this device, I want to know everything, right?

20:58.780 --> 20:59.900
And so that's what you get.

21:00.040 --> 21:08.440
You can say, hey, please walk through, please enumerate everything on the back plane recursively, give me a connection to this identity object, get all its attributes.

21:09.380 --> 21:13.220
Cycle through, give me a connection to that identity object, get all its attributes, on and on and on.

21:13.400 --> 21:23.680
Theoretically, even recursively, you have multiple connections, like one of these things could be another Ethernet IP adapter connecting to another rack, and you could still forward that on, and it might not be speaking Ethernet IP, it might be serial,

21:23.680 --> 21:24.300
it might be whatever.

21:24.300 --> 21:41.460
In fact, as you can see, down there at the bottom, you've got an RS232 connector, you've got a 24 volt DC magic thing that's probably making something cool happen in the real world, but the point is, you can use this to recursively discover everything in a SIP network.

21:41.760 --> 21:45.740
And I think I actually managed to finish on time.

21:45.760 --> 21:47.200
So thank you.

21:47.880 --> 21:50.020
If there's any questions, please, I'll be right here.
