start	end	text
460	1340	Thank you for coming.
1340	2360	My name is Tim Clevenger.
2360	4820	This is Access Control Dunbright the first time.
5380	20460	By day I'm a network cybersecurity engineer, but in a previous life I worked as a sysadmin for an alarm company that did access control systems and they offered to let me get out of the dark server room and go drive a truck around and install, troubleshoot,
20460	25380	maintain access control systems that had been installed by them and by other companies.
25520	40580	And so working on those systems I just came up with a few kind of tips and tricks to make your access control system, whether you're installing a new one, upgrading, or just doing maintenance to make it a little more maintainable, a little more reliable,
40680	41720	a little more secure.
42300	47720	Many vendors, you know, it's a low bid situation and they'll sell you a minimal viable product.
47720	48200	It'll work.
48200	49580	It'll probably open the doors.
49640	56060	But it's usually not the best for your long term security, I would say.
56660	61600	So when you're choosing a system, there's a company called Mercury Security.
61600	65800	They make the majority of the equipment that is in use in the industry.
65960	69560	There's a bunch of companies that will take that equipment and put their name on it.
70020	79160	It has local storage and onboard processing, so the access panels make all of the decisions on whether to open the door based on the cardholder information.
79280	87680	So if your power goes out and comes back on, you don't have to worry about the board losing its memory and having to reload it, unlike some other vendors that are out there.
88180	108100	The cool thing is because it is firmware reflashable and everybody uses the same boards, if you decide, for instance, that you're not going to use the Linel anymore and you want to go with the Genetech or Honeywell, you can have them come reflash the firmware on most of your boards and be able to switch over to another system without having to buy a whole lot of extra equipment.
108680	113700	So this would be a good time to have a video, but I have pictures of a couple of boards here.
113700	116380	So there's essentially two boards that you'll find in the field.
116520	118200	One of them is called the access panel.
118200	124320	Again, this is the board that makes the decisions or most of the decisions about whether to let somebody in a door.
124520	128340	They're typically connected to your network and to your server over Ethernet.
128740	134960	They have a two-door controller built into them as well, so if you only need two doors, you can get away with just a single board.
135460	137580	And then you have what's called a door controller.
137580	143540	And these are dumber boards, they're a lot cheaper, but they don't store a copy of the cardholder database.
143540	157780	So if something happens and they lose connection, they go into a really dumb mode where it's either everybody's allowed, nobody's allowed, or only people with a certain facility code are allowed, even if they left the company ten years ago and didn't turn their card in.
158540	162980	The way that... and here's another good time for a picture.
163140	174400	So a typical installation, you'll have an enclosure mounted to a wall somewhere, you'll have your access panel again connected with Ethernet, and then you'll have one or more door controllers connected to that.
174420	181140	And then you'll have a power supply with a charger built in and a couple of batteries so that if the power goes out, you're still able to open your doors.
181960	193280	So first thing to consider when you're looking at an access control system and you're working with a project manager at the company or you're putting out an RFP is, where in my building am I going to place my equipment?
193420	198380	So some considerations for that would be like environments, you know, heat, humidity, and dust.
198540	210040	I had to go to work on a system for an HOA and replace the board in one of their pools, their common pools, because it wasn't working reliably when I opened the door.
210040	216080	It's all crusty because they put it in the same room that they put their saltwater pool filtration system.
216200	217900	You're not going to warranty that board.
217900	219420	You're going to have to buy a new one.
220160	221880	Power availability is another one.
221880	223640	Obviously, don't just plug it into an outlet.
223640	226980	You want something that's hardwired with its own circuit breaker.
227320	230000	Physical security, is this going to be in a hallway?
230000	233860	Is it going to be in a closet where maybe unauthorized people are going to get in there?
234240	243720	Maybe put a lock on there and a tamper switch so that it's easy to protect it from somebody just opening the door and tearing out wires.
244060	245560	And then future accessibility.
246040	260220	A lot of times you'll find remote equipment that has been installed by the vendor and they just stick it up in the ceiling and then later it gets drywalled over and then there's wallpaper and if you have to get to that, you're going to, you know, pay somebody to have to fix that up.
261020	265520	So when you're making that decision, I'm going to talk a little bit about wiring.
265520	272440	So you have wiring from your access panel, which again makes all the decisions, to your individual door controllers.
272500	278040	So door controllers, that communication is done with a protocol called RS-485.
278140	279820	It's a protocol from the 80s.
279820	286160	It's typically a 2-wire or 4-wire cable that connects from the panel to the door controller.
286160	292620	There's a shield that has to be like drained at one end and then there's termination at the end of a string.
292780	295780	The theoretical distance is 4,000 feet.
295780	304080	So the first thought from any vendor is, oh, we'll just put a panel here and then we'll just run, you know, 4,000 feet of wires to all of these door controllers.
304080	306000	The problem is they're daisy-chained.
306000	309800	So you go from your panel to your door controller to your door controller to your door controller.
309880	330240	If that wire gets cut in the middle or there's electromagnetic interference because somebody's put a transformer on the other side of the wall, you lose the entire string and then you have to troubleshoot where in all of these devices in this long line of thousands of feet is the problem that's causing me to lose access to all 31 of my door controllers.
330640	340140	So one fault anywhere in there, and that could also mean a failed door controller that's, you know, causing problems on the line, can cause a real issue.
340860	346300	Then you have to think about the controller, the wiring from that door controller to the actual doors.
346440	352760	The card reader wiring also uses RS-485 for newer installations, so there's some consideration there.
352760	363380	But also you have kind of power-hungry locks like magnetic locks or crash bars that can use a lot of electricity and then you're putting a remote power supply out there.
363380	367800	So you kind of have to decide where in my building can I minimize all of these issues.
368500	370440	And then also wire quality.
370440	382880	So typically what I see is a lot of kind of whatever was on the truck or whatever we got at a discount from the place that we buy our wire is going to be what we're going to use.
382880	392280	So the power to our door lock, well, it's a little far for this 18-gauge wire, but we're going to go ahead and run it anyway because that's what we've got.
393100	400340	I've seen spliced wire where they've just kind of, you know, they ran out of wire or something and they spliced it together and maybe it got cut or something.
400660	410760	A lot of unshielded wire, again, for card readers, this is particularly an issue where the card reader can crash and you actually have to unplug it from the panel to get it to start working again.
410760	416720	And then just plain unsuitable wire, like I've seen Ethernet wire used for wiring this stuff.
417800	421680	So the answer to that is called composite access control cable.
421680	427280	It's made by companies that design this for access control applications.
427280	428940	It has all the wires that you need.
428940	430880	They're all shielded where they need to be shielded.
430880	437400	You can get them with auxiliary and spare conductors if you want to run a push button or other stuff.
437400	441340	They're properly shielded, as I mentioned, and then there's like a thick exterior jacket.
441500	449160	But the important thing is if somebody has run this access control cable, you can look at it immediately and go, okay, this is suitable cable.
449160	455360	I don't have to, like, go figure out did they run, you know, too thin a cable for this particular wiring run.
456240	459600	And again, a little bit about those remote power supplies.
459600	461700	They're required for power hungry locks.
461860	470760	Magnetic door locks are the worst for this because if you get too much of a voltage drop, then somebody can just pull on the door really hard and it'll open, but it looks like it's locked.
471520	475960	And what'll happen is sometimes they'll run wire and they'll realize, oh, this is too far.
475960	481880	We're just gonna put a remote power supply up in the ceiling somewhere above a conference room, maybe above the door.
481960	484560	Not necessarily tell you that it's there.
484580	489800	And then when the power goes out and that one door doesn't work, you have to figure out why it is.
489800	492580	And they'll use the cheapest enclosure, the cheapest power supply.
492580	493860	They won't put batteries on it.
493860	495280	It won't have a tamper switch.
495720	501680	So, again, it's something that when you're looking at your layout with your project manager, you can go, okay, this looks like a really long run.
501680	504220	Am I gonna need to do a remote power supply?
504220	508200	If so, let's pick the model and everything right here and make sure it gets batteries.
508200	509620	Make sure it gets documented.
509760	513920	Make sure it's someplace where, again, we're not gonna have to tunnel through a ceiling to get to it.
515220	521560	The preferred layout, at least in my opinion, having done a few of these, is to kind of cluster your equipment.
521560	523280	So, you get a large enclosure.
523720	524860	Hey, hey.
526180	531400	Hi, my name is Tim Clevenger.
531400	537600	This is access... So, this is kind of the preferred way that you want to do this.
537600	543000	You want to cluster your equipment into a single enclosure or a couple of enclosures near each other.
543380	545100	You have your access panel at the top.
545100	546360	You have door controllers.
546360	548700	And you run all your door wiring out from there.
549240	556960	The nice thing about this is, all of your RS-485 wiring, well, in this particular enclosure, it's pre-wired, which is even better.
556960	559260	But it's all nice short runs.
559280	563620	If something happens in here, it's real easy to troubleshoot because it's all right there in one place.
565020	572820	So, typically in an office scenario, you know, you're gonna have, this is like a class A office in a high rise where you have essentially two halves of a building.
572820	575580	There's elevators in the middle that are kind of the common area.
575780	583240	And so, generally, what you want to do is kind of have that cluster just somewhere near the center of the floor.
584520	587320	Don't run RS-485 to another floor.
587420	588740	Don't ask me how I know.
589500	596020	Have that kind of centralized there and maybe you've got to do a remote power supply at the far end if this were a much bigger floor.
596020	599300	But in a situation like this, again, it's all centrally located.
599460	609780	Or, for instance, you might have, I don't know, a pandemic that causes a bunch of folks to work from home and you've got this extra office space that maybe you want to sublease half a floor.
609780	617360	So, maybe when you get this space, you plan out, okay, I'm gonna do a cluster over here that controls this side, a cluster over there that controls that side.
617360	626160	And that way, if we need to sublease it, we can just cut one wire, put up some doors to block off one half of the office space, and then you've still got your half of the office.
626240	632920	And if the sublease ever ends, then you just run the Ethernet again to that access panel, reprogram everything and you're up and running with a whole floor again.
633820	638140	Now, there are some cases where you're gonna be doing RS-485.
638140	650940	So, here, for instance, you know, you have like a warehouse with, you know, 70, 80, 90 docks and, you know, a person door every 10 docks so that, you know, you have a fire escape and maybe somebody can talk to a driver and go back in.
651260	656480	Well, your Ethernet is gonna be, you know, 328 feet is the maximum that you can go.
656480	672660	So, you probably are gonna have to put your access panel at one end and run door controllers just kind of linearly along the wall above all of these doors with a drop every, you know, every 10 doors to be able to open that person door from the outside.
673120	674880	The wiring's exposed.
674880	677920	It's not, you know, there's no EMI, there's no rats up there.
677920	680600	It's real easy to troubleshoot and figure out that way.
680600	692920	So, in that case, you're probably, rather than trying to, like, do Ethernet to all of these and fiber media converters and everything to try to reach, you know, 800 or 1,000 feet, just do that single run of RS-485.
693300	705220	And then you have the gate way at the far end of the parking lot and you've got everything in your building all nice and clustered, you know, one or two clusters on each floor, but you've got that gate out there with a card reader.
705880	708560	Probably your best bet's gonna be RS-485 for that.
708580	712300	Unless you've got a guard shack that has Ethernet, then maybe you do a panel.
712560	714960	But, again, you're running it in a conduit underground.
714960	716360	You can go up to 4,000 feet.
716360	719700	It's one drop because you only need one door controller at the far end.
719700	725260	It's gonna be much more reliable than, you know, having to do it any other way.
726640	739340	So, when you're doing these panels in the enclosures, and this goes for remote power supplies as well, you'll find that, again, we're doing this low-bid, minimum viable product.
739680	749580	These enclosures typically have tamper switches, so if somebody prys open the cover on the thing, you get an alert in your system and you can send somebody out to go figure out who's opened this up and why.
749840	751860	And also this goes for card readers.
751860	759860	There are numerous attacks against card readers, and the first thing that they do is pull the card reader off the wall and attach something to the wires and put it back on the wall.
759860	763060	If you have a tamper, at least you know that that's happened.
763580	776160	And also for a Knox box where you have a key stored, having a tamper on that, again, just helps if somebody prys it off the wall, you know immediately and can disable the card or, you know, rekey the locks or whatever you need to do there.
776420	787400	And typically they just won't do this connection, so make sure that you have that in your RFP or when you're talking to your, you know, your project manager, your salesperson, make sure that you've got that squared away.
787400	797120	I want AC fail, I want battery fail contacts, so that if the power goes out for that one panel for some reason, I know about it instead of waiting for the door to stop working.
799440	808100	I talked a little bit about some of the better locking hardware to deal with motorized crash bars and multi-point locks where you have a lock on the top and the bottom.
808520	811580	And magnetic locks especially take a lot of electricity.
811780	823900	So if you're going to do a long run, you have to look at maybe I'm going to do a remote power supply, maybe I'm going to do 24 volts to this instead of 12 volts because I can use the same wire and run essentially twice the power to it.
824240	834420	But it's something that you need to consider because again a magnetic lock, a lot of times if that thing's got some voltage drop, it'll look like it's locked and it'll rattle like it's locked, but if you pull hard enough it'll just pop open.
835060	837460	And then any doors that have solenoids.
837460	842840	I've seen this happen a few times, just kind of standard solenoid unlocked doors.
842920	850180	If you have, you know, this door is unlocked during business hours, eight to ten or twelve hours a day, you may notice that the handle feels warm.
850280	857780	It's because that solenoid is constantly activated during business hours and it can fail on you and then you can't open the door at all.
857860	863980	So it's just something to keep an eye out for and make sure you have something that, you know, maybe is better suited for that particular door.
865260	874940	You know, motion sensors are used to determine whether somebody is leaving, opening the door from the inside legitimately as opposed to prying it open from the outside.
875400	880300	They generally require separate power, so make sure that you're accounting for that when you're running your wire.
880960	887720	They have a, you know, essentially heat or infrared or microwave or both as a way that they detect movement.
888500	890740	Aim and detection range is important on these.
891060	900380	First of all, because there's bypasses, you know, you can do the spray through the doors or the, you know, under the handle door opening.
900680	905240	Or you can get false trips, which, you know, sends a guard out there for no reason.
905500	916580	You also have, you know, this thing is aimed at a door, but it's in a hallway, and every time somebody walks by, it goes click, click, click, click, click, which, you know, drives people crazy who are sitting near it.
918540	923380	So those door sensors I was talking about, a door contact, so that detects if the door is open or closed.
923380	934420	And the REX, or request to exit, that, again, is a micro switch or a motion detector or even a push button that says this door is about to open legitimately from the inside with somebody leaving.
934460	936220	There's bypasses for all of those.
936220	940100	Again, kind of think about that when you're deciding what you want to do there.
940320	944360	What is almost never done are supervision resistors.
944420	955480	These are basically put in line as close to the door contact as possible, and what they do is they change the signal from either this line is open and this line is shorted.
955480	959200	It changes it to four different resistance levels.
959200	963360	This line is shorted, this line is opened, or the door is open or the door is closed.
963480	975000	So it allows you to, it allows the system to detect, again, if somebody, you know, cuts the wires or splices them together or the door contact falls off, it helps you troubleshoot that a little bit better.
975000	976600	These things are like a buck and a half.
976600	979600	It is sheer laziness that companies do not install these.
981860	984860	A little bit about life safety, because that's very important.
985300	987800	There's fail-safe versus fail-secure locks.
987800	999520	And what that means is, if the software crashes, is this door going to fail safe, meaning that somebody can open the door to get out, or is it going to fail secure where the door is not going to open?
1000100	1004340	Always make sure that you set that up to allow people to escape.
1004460	1008100	It's never worth risking people's lives to protect property.
1008920	1013320	Coordinate with your local fire code and your authority having jurisdiction.
1013460	1022520	Some areas, that's a fire marshal, sometimes it's a building inspector, but make sure that you have a way for people to escape if there's an emergency.
1023200	1038540	If you are in a high-rise building, again, you'll have a building fire alarm, and usually part of your lease, and probably part of the fire code, is that you connect your system using these relays so that if the fire alarm goes off, it automatically unlocks doors so that people can escape.
1039020	1041320	And then finally, a Knox box, you may have seen these.
1041320	1043720	They're typically attached to the outside of the building.
1043740	1051980	They have a special key that the fire department, and probably bad guys have, that they can open it up and get a key or a card out of there to get into a building in case of an emergency.
1052240	1057000	Again, I would put a tamper on that, because you really don't know who's cloned that key or who has that key.
1059120	1062040	So, a little quick thing about badges and readers here.
1063540	1069500	Badge readers come in different shapes and sizes and strengths, depending on what you're going to be reading.
1069640	1072920	Additional factors, including biometrics and pin entry, are available.
1072920	1086580	I typically love to have pin entry on high security doors, like maybe your server room, because it keeps anybody from having cloned or stolen a badge from immediately getting in, unless somebody wrote the pin on the back of the card.
1087960	1089680	There's different badge types.
1089680	1091240	I only have a few here.
1091240	1094240	The 125 kilohertz prox, those are really trivial to break.
1094240	1098120	Those are the ones you get from your gym and your apartment complex's parking garage.
1098120	1100300	They're the cheapest systems that you can get.
1100420	1105420	The higher frequency iClass ones are also pretty well broken by now.
1105480	1110720	There are some others, like the Desfire V2 and above, that's maybe not broken.
1110720	1114720	There's some kind of workarounds on some of these.
1114780	1117500	And then the HIDCOS is also not broken.
1117520	1120160	Again, asterisk.
1121700	1125780	So, the prox and the iClass, they have a facility code and a badge ID.
1126140	1132780	You have 256 facility codes to choose from in the 26-bit format.
1132940	1140040	You can buy the cards from your vendor or eBay or other places with the facility code that you want.
1140040	1150300	For some reason, I've seen more than any other codes, obviously one, but I've also seen 132 as a code that a lot of people get.
1150300	1152700	So, maybe don't get those.
1153500	1156160	Again, prox and iClass, you can clone them.
1156160	1158960	Any compatible reader that you get off eBay can read those cards.
1159040	1166840	And then the data can be captured from a portable reader, like one that you attach to batteries and stick in a briefcase and go get people's cards.
1167360	1169560	The solution for that is custom badges.
1169560	1170780	Again, there's many different ones.
1170780	1171980	These are the ones I'm familiar with.
1171980	1174040	It's called HID Corporate 1000.
1174340	1177560	It's COS compatible, so it's more secure.
1177840	1179480	You get a dedicated facility code.
1179480	1186920	Nobody can order that same facility code except for specific employees from your company from your preferred vendor.
1187260	1191540	And because it's a 48-bit format, you have 8 million badge numbers to choose from.
1191540	1197760	So, you can pick a range from way up high and not have to worry about acquiring a competitor.
1197760	1199600	Then you've got the same badge numbers.
1200060	1203780	When you use a system like this, make sure you disable the older formats.
1203780	1206540	Otherwise, people can still use an old prox.
1207860	1211800	So, Badger Communications Weekend is the one that's still being used.
1211800	1212860	It's from 1975.
1212860	1215680	It's a year older than I am, and it's still being used.
1216580	1219120	Again, very trivial to capture.
1219120	1220060	Pull the reader off the wall.
1220060	1221540	Attach one of these devices on there.
1221540	1225180	It'll send it to you over Wi-Fi while you're outside the property.
1225360	1231060	The fix here is tamper switches and OSDP, which is the Open Supervised Device Protocol.
1231060	1232660	It's from 2015.
1232660	1233860	It has encryption.
1233860	1238400	You have to actually enroll your badge readers so that they communicate over an encrypted protocol.
1238480	1240380	Again, it's RS-485.
1240380	1242180	You can daisy-chain readers.
1242320	1243040	Please don't.
1243040	1246840	There's only very specific circumstances where you're going to want to do something like that.
1246920	1248520	It's not perfect.
1248600	1252040	There is a compromise possible while you're doing the reader pairing.
1252080	1257240	If somebody on the other side has a... it's one of those, like, unlikely ones.
1257300	1263580	But the biggest problem is 84% of installers, as of a couple years ago, never or seldom use it.
1263580	1265720	They're still using the old Wiegand.
1267180	1269260	So what else should I do?
1269260	1271120	Test your readers regularly.
1271260	1273960	Make sure that those are working correctly.
1274420	1275940	Set up alerts in your system.
1275940	1282400	It does you no good to spend all this money on an access control system if it generates alerts that go nowhere.
1282460	1283400	Have it send an email.
1283400	1290520	If you can't have a guard or somebody responsible for that, just have it send email alerts to a bunch of people and somebody can go check the door.
1290820	1292140	These systems are really cool.
1292140	1299460	You can link them up with a camera system so that if something happens on a door, it can bring up a view of that exact camera.
1299460	1300640	Like, do it.
1300640	1302780	It's definitely worth it.
1303060	1309660	Document not only, you know, where your badge readers are, but where those remote power supplies are, where the batteries are.
1310260	1315820	Check those batteries after three to five years is usually when you replace them.
1315820	1317700	They're typical UPS batteries.
1317700	1319320	They're really cheap from Home Depot.
1319660	1325280	If it's in a hot room, then check them every, you know, replace them every three years.
1325280	1327740	If it's in an air conditioned room, replace them every five years.
1328060	1331900	And then I haven't gone into any bypasses, but there's lots of that stuff.
1331900	1333400	So come to the physical security village.
1333400	1338800	We've got all kinds of demos set up there for you to take a look at.
1339060	1341120	I have an RFP on my GitHub.
1341120	1342900	This RFP has everything.
1343220	1344400	So feel free to look at it.
1344400	1358060	Pick and choose the stuff that's important to you to put in your RFP or to talk to your project manager about to build the system the way that you think it should be built.
1358060	1361820	But don't accept the defaults, because the defaults are never good.
1362720	1363580	Thank you so much.
1363580	1364780	I really appreciate it.