peter bassill · operator
$ cve CVE-2017-14470 JSON

CVE-2017-14470

10.0
CRITICAL · CVSS 3.0 · EPSS 38% (pctl 99)

Patch early

EPSS 38% — above the 10% action threshold.

Description

An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG or RUN Description: The value 0xffffffff is considered NaN for the Float data type. When a float is set to this value and used in the PLC, a fault is triggered. NOTE: This is not possible through RSLogix.

Scoring

CVSS10.0 (CRITICAL, v3.0)
VectorCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H
EPSS37.97% — more likely to be exploited than 99% of all CVEs
On CISA KEVno
Public exploitnone known
Published2018-04-05
Last modified2026-06-17

Affected (2)

VendorProduct
rockwellautomationmicrologix 1400
rockwellautomationmicrologix 1400 b firmware

References

→ the Explorer  ·  watch your stack  ·  NVD