CVE-2019-6572
In your normal cycle
Critical by CVSS (9.1), but no sign of active exploitation.
Description
A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15.1 Update 1), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15.1 Update 1), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Advanced (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Professional (All versions < V15.1 Update 1), SIMATIC WinCC (TIA Portal) (All versions < V15.1 Update 1), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). The affected device offered SNMP read and write capacities with a publicly know hardcoded community string. The security vulnerability could be exploited by an attacker with network access to the affected device. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise confidentiality and integrity of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.
Scoring
| CVSS | 9.1 (CRITICAL, v3.1) |
|---|---|
| Vector | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N |
| EPSS | 2.72% — more likely to be exploited than 86% of all CVEs |
| Weakness | CWE-200 |
| On CISA KEV | no |
| Public exploit | none known |
| Published | 2019-05-14 |
| Last modified | 2026-06-17 |
Affected (22)
| Vendor | Product |
|---|---|
| siemens | simatic hmi comfort outdoor panels |
| siemens | simatic hmi comfort outdoor panels firmware |
| siemens | simatic hmi comfort panels |
| siemens | simatic hmi comfort panels firmware |
| siemens | simatic hmi ktp mobile panels ktp400f |
| siemens | simatic hmi ktp mobile panels ktp400f firmware |
| siemens | simatic hmi ktp mobile panels ktp700 |
| siemens | simatic hmi ktp mobile panels ktp700 firmware |
| siemens | simatic hmi ktp mobile panels ktp700f |
| siemens | simatic hmi ktp mobile panels ktp700f firmware |
| siemens | simatic hmi ktp mobile panels ktp900 |
| siemens | simatic hmi ktp mobile panels ktp900 firmware |
| siemens | simatic hmi ktp mobile panels ktp900f |
| siemens | simatic hmi ktp mobile panels ktp900f firmware |
| siemens | simatic hmi mp |
| siemens | simatic hmi mp firmware |
| siemens | simatic hmi op |
| siemens | simatic hmi op firmware |
| siemens | simatic hmi tp |
| siemens | simatic hmi tp firmware |
| siemens | simatic wincc \(tia portal\) |
| siemens | simatic wincc runtime |
References
- http://www.securityfocus.com/bid/108412
- https://cert-portal.siemens.com/productcert/pdf/ssa-804486.pdf
- https://www.us-cert.gov/ics/advisories/ICSA-19-134-09
- http://www.securityfocus.com/bid/108412
- https://cert-portal.siemens.com/productcert/pdf/ssa-804486.pdf
- https://www.us-cert.gov/ics/advisories/ICSA-19-134-09
→ the Explorer · watch your stack · NVD